User Manual

Note:
The radar sensor with rinsing air connection or antenna exte nsion is
provided with a notch on the antenna socket. This notch must
correspond to the marking on the hexagon of the process tting (the
marking species the position of the polarisation level of the radar
signal).
3
4
1
2
Fig. 2: Dismounting of the horn antenna
1 Marking of the polarisation plane
2 Notch at the antenna socket
3 Hexagon screws on the antenna socket
4 Antenna
4.3 Mounting preparations - Parabolic antenna
The instrument is also available in versions where the antenna has a
diameter larger than the process tting (thread, ange). With such
versions the antenna must be disconnected from the process tting
before mounting. Proceed as follows:
1 Clamp VEGAPULS 62 with the ange, e.g. in a bench vice
2 Hold the connection piece (3) with a wrench (width across ats 22)
on the attenings
3 Loosen counter nut (2) completely with a wrench (width across
ats 36) in the antenna direction
4 Loosen compression nut (1) completely with a wrench (width
across ats 41) in the antenna direction
5 Remove the parabolic antenna (4) axially
6 Mount sensor ange to the adapter ange and clamp it
7 Check, if the O-ring seal is available on the connection piece and if
it is not damaged.
12 VEGAPULS 62 4 20 mA/HART two-wire
4 Mounting
36503-EN-100607