User Manual

10 mm
>
Fig. 8: Recommended socket mounting
If the reective properties of the medium are good, you can mount
radar sensor on sockets which are higher than the length of the
antenna. You will nd recommended values for socket heights in the
following illustration. The socket end should be smooth and burr-free, if
possible also rounded. After installation you must carry out a false
echo storage.
d
h
max.
d
1½"
50 mm/2"
80 mm/3"
100 mm/4"
150 mm/6"
200 mm
250 mm
300 mm
500 mm
800 mm
h
max.
Fig. 9: Deviating socket dimensions
Tip:
The instrument is optionally also available with antenna extension.
Hence the antenna length can be selected such that the antenna end
protrudes 10 mm (0.4 in) out of the socket.
In liquids, align the sensor as vertical as possible to the product
surface to achieve optimum measuring results.
Orientation of the sensor
16 VEGAPULS 62 4 20 mA/HART two-wire
4 Mounting
36503-EN-100607