User Manual

If screened cable is necessary, connect the cable screen on both ends
to ground potential. In the sensor, the screen must be connected
directly to the internal ground terminal. The ground terminal on the
outside of the housing must be connected to the potential equalisation
(low impedance).
If potential equalisation currents are expected, the connection on the
processing side must be made via a ceramic capacitor (e. g. 1 nF,
1500 V). The low frequency potential equalisation currents are thus
suppressed, but the protective eect against high frequency interfer-
ence si gnals remains.
Warning:
Within galvanic plants as well as vessels with cathodic corrosion
protection there are considerable potential dierences. Considerably
equalisation currents can be caused via the cable scrren when the
screen is earthed on both ends. To avoid this, the cable screen must
only connected to ground potential on one side of the switching
cabinet in such applications. The cable screen must not be connected
to the internal ground terminal in the sensor and the outer ground
terminal on the housing not to the potential equalisation!
Information:
The metal parts of the instrument (antenna, transmitter, concentric
tube, etc.) are conductive connected with the inner and outer ground
terminal on the housing. This connection exists either directly metallic
or with instruments with external electronics via the screen of the
special connection cable. You can nd specications to the potential
connections within the instrument in chapter "Technical d ata".
5.2 Connection
The connection of the voltage supply and the signal output is carried
out via the spring-loaded terminals in the housing.
The connection to the indicating and adjustment module or to the
interface adapter is carried out via contact pins in the housing.
Proceed as follows:
1 Unscrew the housing cover
2 If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.
3 Loosen compression nut of the cable entry
4 Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
Cable screening and
grounding
Connection technology
Connection procedure
26 VEGAPULS 62 4 20 mA/HART two-wire