6.3 Parameter adjustment
With the parameter adjustment, the instrument is adapted to the
application conditions. The parameter adjustment is carried out via an
adjustment menu.
Information:
In this operating instructions manual, the instrument-specific param-
eters are described. Further general parameters are described in the
operating instructions manual "Indicating and adjustment module".
The main menu is divided into five areas with the following functions:
Setup: Settings, for example, to measurement loop name, medium,
application, vessel, adjustment, signal output
Display: Language setting, settings for the measured value indication
as well as lighting
Diagnosis: Information, for example to the instrument status, pointer,
reliability, simulation, echo curve
Further settings: Unit, false signal suppression, linearisation curve,
reset, date/time, reset, HART mode
Info: Instrument name, hardware and software version, calibration
date, instrument features
In the main menu point "Setup", the individual submenu points should
be selected subsequently and provided with the correct parameters to
ensure the optimum adjustment of the measurement. The procedure is
described in the following.
Setup
Each medium has different reflection properties. With liquids, further
interfering factors are fluctuation product su rface and foam generation.
With bulk solids, these are dust generation, material cone and
additional echoes from the vessel wall.
To adapt the sensor to these different measuring conditions, the
selection "Liquid" or "Bulk solid" should be made in this menu item.
Main menu
Setup/Medium
VEGAPULS 62 • 4 … 20 mA/HART two-wire 33