User Manual

Through this selection, the sensor is adapted perfectly to the product
and measurement reliability, particularly in products with poor
reective properties, is considerably increased.
Enter the requested parameters via the a ppropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
In addition to the medium, also the application or the application place
can inuence the measurement.
With this menu item, the sensor can be adapted to the applications.
The adjustment possibilities depend on the selection "Liquid" or "Bulk
solid" under "Medium".
The following options are available when "Liquid" was selected:
Caution:
If in the vessel, there is a separation of liquids with dierent ε
r
value, for
example by condensation, the radar sensor can detect under certain
circumstances only the medium with the higher dielectric value. Keep
in mind that interfaces can cause faulty measurements.
If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially
designed for interface measurement.
Setup/Application
34 VEGAPULS 62 4 20 mA/HART two-wire
6 Set up with the indicating and adjustment module
36503-EN-100607