User Manual

Setup: Resetting of the parameter settings to the default values of the
respective instrument in the menu item Setup. Order-related settings
remain but are not taken over into the current parameters. User-
generated false signal suppression, user-programmed linearization
curve, measured value memory as well as event memory remain
untouched. The linearization is set to linear.
False signal suppression: Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values distance: Resetting the measured min. and max.
distances to the actual measured value.
The following table shows the default values of the instrument.
Depending on the instrument version, not all menu items are available
or dierently assigned:
Menu Menu item Default value
Setup Measurement
loop name
Sensor
Medium Liquid/Water
Bulk solids/Crushed stones, gravel
Application Storage tank
Silo
Vessel form Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"Technical data" in the supplement
Min. adjustment Recommended measuring range, see
"Technical data" in the supplement
Max. adjustment 0,000 m(d)
Damping 0.0 s
Current output
mode
4 20 mA, < 3.6 mA
Current output
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Lock operation Released
Display Language According to order
Displayed value Distance
Display unit m
Scaling size Volume
l
40 VEGAPULS 62 4 20 mA/HART two-wire