User Manual

1
2 4
3
OPEN
TWIST
USB
LOCK
Fig. 28: Connecting the PC via HART to the signal cable
1 Sensor
2 HART resistance 250 Ω (optional depending on processing)
3 Connection cable with 2 mm pins and terminals
4 Processing system/PLC/Voltage supply
5 Interface adapter, for example VEGACONNECT 4
Note:
With power supply units with integrated HART resistance (internal
resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e.g. to the VEGA instruments VEGATRENN
149A, VEGAMET 381, VEGAMET 391. Common Ex separators are
also usually equipped with a sucient current limitation resistance. In
such cases, the interface converter can be connected parallel to the
4 20 mA cable (in the previous illustration dashed).
7.2 Parameter adjustment with PACTware
As an alternative to the indicating and adjustment module, the sensor
can also be congured via a Windows PC. For this purpose, the
conguration software PACTware and a suitable instrument driver
(DTM) according to the FDT standard are required. The actual
PACTware version as well as all available DTMs are compiled in a
DTM Collection. Furthermore the DTMs can be integrated in other
frame applications according to the FDT standard.
Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functions are included in older rmware versions. The latest instrument
software can be also downloaded from our homepage. A description of
the update procedure is also available in the Internet.
Further setup steps are described in the operating instructions manual
"DTM Collection/PACTware" attached to each DTM Collection and
which can also be downloaded from the Internet. Detailed descriptions
are available in the online help of PACTware and the DTMs.
Via the interface adapter
and HART
Prerequisites
VEGAPULS 62 4 20 mA/HART two-wire 43
7 Setup with PACTware
36503-EN-100607