User Manual

Code
Text mes-
sage
Cause Removal
F025
Error in the li-
nearization
table
l Index markers are not
continuously rising, for
examle unlogical value
pairs
l Check linearization table
l Delete table/Create new
F036
No operable
software
l Failed or interrupted soft-
ware update
l Repeat software update
l Check electronics version
l Exchange the electronics
l Send instrument for repair
F040
Error in the
electronics
l Hardware defect l Exchange the electronics
l Send instrument for repair
F080 l General software error l Separate operating voltage
briey
F105
Determine
measured va-
lue
l The instrument is still in the
start phase, the measured
value could not yet be
determined
l Wait for the warm-up phase
l Duration depending on the
version and parameter ad-
justment up to approxima-
tely 3 min.
F125
Unpermissible
electronics
temperature
l Temperature of the elect-
ronics in the not specied
section
l Check ambient temperatu-
re
l Isolate electronics
l Use instrument with higher
temperature range
F260
Error in the
calibration
l Error in the calibration car-
ried out in the factory
l Error in the EEPROM
l Exchange the electronics
l Send instrument for repair
F261
Error in the
conguration
l Error during setup
l False signal suppression
faulty
l Error when carrying out a
reset
l Repeat setup
l Repeat reset
F264
Installation/S-
etup error
l Adjustment not within the
vessel height/measuring
range
l Max. measuring range of
the instrument not suci-
ent
l Check or correct installa-
tion and/or parameter ad-
justment
l Use an instrument with
bigger measuring range
F265
Measurement
function dis-
turbed
l Sensor does no longer
carry out a measurement
l Operating voltage too low
l Check operating voltage
l Carry out a reset
l Separate operating voltage
briey