User Manual

The following table shows the codes and text messages of the status
message "Function check" and provides information on causes as well
as corrective measures.
Code
Text mes-
sage
Cause Removal
C700
Simulation
l Simulation active l Finish simulation
l Wait for the automatic end
after 60 mins.
The following table shows the codes and text messages of the status
message "Out of specication" and gives instructions for the reason
and removal.
Code
Text mes-
sage
Cause Removal
S600
Unpermissible
electronics
temperature
l Temperature of the elect-
ronics in the not specied
section
l Check ambient temperatu-
re
l Isolate electronics
l Use instrument with higher
temperature range
The following table shows the codes and text messages of the status
message "Maintenance" and provides information on causes as well
as corrective measures.
Code
Text mes-
sage
Cause Removal
M500
Error with the
reset delivery
status
l With the reset to delivery
status, the data could not
be restored
l Repeat reset
l Load XML le with sensor
data into the sensor
M501
Error in the
non-active li-
nearization
table
l Hardware error EEPROM l Exchange the electronics
l Send instrument for repair
M502
Error in the
diagnosis me-
mory
l Hardware error EEPROM l Exchange the electronics
l Send instrument for repair
Function check
Out of specication
Maintenance (mainte-
nance requirement)
VEGAPULS 62 4 20 mA/HART two-wire 49