User Manual
l Current sensor software as file
Caution:
Keep in mind that a software update can lead to expiry of the
approvals. You can find detailed information on our homepage
www.
vega.com.
At "
www.vega.com/downloads" go to "Software". Select under "plics
sensors and instruments" the respective instrument series and
software version. Load the zip file via the right mouse key with "Save
target as" e.g. on the desktop of your PC. Extract all files available in
the zip file, e.g. to the desktop.
Connect the sensor to power supply and provide connection from the
PC to the instrument via the interface adapter. Start PACTware and
move via the menu P roject to the VEGA pr oject assistant. Select
"USB" a nd "Set instruments online". Provide connection to the sensor
via "Start" until the message "Search complete" is displayed.
Move in the PACTware menu bar to "Instrument data", "Additional
functions" and "Software update". PACTware now checks the actual
hardware and software version of the sensor and displays the data.
This process takes approx. 60 s.
Push the button "Update software" and select the previously extracted
XML file. Then the software update can be started. The additional files
are installed automatically. Depending on the sensor, this procedure
lasts approximately 15 min.
9.7 How to proceed in case of repair
If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage
www.vega.com under: "Downloads - Forms and certificates - Repair
form".
By doing this you help us carry out the repair quickly and without
having to call back for needed information.
l Print and fill out one form per instrument
l Clean the instrument and pack it damage-proof
l Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
l Please ask the agency serving you for the address of your return
shipment. You can find the competent agency on our website
www.vega.com.
Load sensor software to
PC
Prepare update
Load software into sen-
sor
52 VEGAPULS 62 • 4 … 20 mA/HART two-wire
9 Diagnosis and service