4 Mounting
VEGAPULS 62 • 4 … 20 mA/HART - two-wire
36503-EN-161221
4 Mounting
4.1 General instructions
Oninstrumentswiththreadedprocesstting,thehexagonmustbe
tightenedwithasuitablewrench.Fortheproperwrenchsizesee
chapter "Dimensions".
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Protect your instrument against moisture ingress through the following
measures:
Use the recommended cable (see chapter "Connecting to power
supply")
Tighten the cable gland
Whenmountinghorizontally,turnthehousingsothatthecable
gland points downward
Loop the connection cable downward in front of the cable gland
This applies mainly to outdoor installations, in areas where humidity is
expected (e.g. through cleaning processes) and on cooled or heated
vessels.
Make sure that all parts of the instrument exposed to the process are
suitable for the existing process conditions.
These are mainly:
Active measuring component
Processtting
Process seal
Process conditions are particularly:
Process pressure
Process temperature
Chemical properties of the medium
Abrasionandmechanicalinuences
Youcannddetailedinformationontheprocessconditionsinchapter
"Technical data" as well as on the type label.
Metric threads
In the case of instrument housings with metric thread, the cable
glands are screwed in at the factory. They are sealed with plastic
plugs as transport protection.
You have to remove these plugs before electrical connection.
NPT thread
In the case of instrument housings with self-sealing NPT threads, it is
not possible to have the cable entries screwed in at the factory. The
free openings for the cable glands are therefore covered with red dust
protection caps as transport protection. The dust protection caps do
notprovidesucientprotectionagainstmoisture.
Screwing in
Protection against mois-
ture
Suitability for the process
conditions
Cable glands