49
6 Set up with the display and adjustment module
VEGAPULS 62 • 4 … 20 mA/HART - two-wire
36503-EN-161221
100%
0%
0,5 m
(19.68
")
5 m
(196.9
")
2
1
3
Fig. 37: Parameter adjustment example min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
3 Reference plane
If these values are not known, an adjustment with the distances of e.g.
10%and90%ispossible.Startingpointforthesedistancespecica-
tionsisalwaysthesealingsurfaceofthethreadorange.Youcannd
specicationsonthereferenceplaneinchapter"Technical data". The
actual level is calculated on the basis of these settings.
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Proceed as follows:
1. Select the menu item "Setup" with [->]andconrmwith[OK].
Now select with [->] the menu item "Min. adjustment"andconrm
with [OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
Setup - Min. adjustment