6 Set up with the display and adjustment module
VEGAPULS 62 • 4 … 20 mA/HART - two-wire
36503-EN-161221
In delivery status, the PIN is "0000".
In this menu item, the internal clock of the sensor is adjusted.
With a reset, certain parameter adjustments carried out by the user
are reset.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
mentfromthefactoryincl.theorder-specicsettings.Acreatedfalse
signalsuppression,user-programmablelinearizationcurveaswellas
the measured value memory will be deleted.
Basic settings: Resetting of the parameter settings, incl. special
parameters, to the default values of the respective instrument. Any
stored false signal suppression or user programmable linearisation
curve, as well as the measured value memory, is deleted.
Setup: Resetting of the parameter settings to the default values of the
respective instrument in the menu item Setup. User-generated false
signal suppression, user-programmed linearisation curve, measured
value memory as well as event memory remain untouched. The
linearisation is set to linear.
False signal suppression: Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values, measured value: Resetting of the measured min. and
max. distances to the actual measured value.
The following table shows the default values of the instrument. De-
pending on the instrument version, not all menu items are available or
somemaybedierentlyassigned:
Additional adjustments -
Date/Time
Additional adjustments
- Reset