4 Mounting
VEGAPULS 69 • 4 … 20 mA/HART - two-wire
47247-EN-170315
d
a
α
Fig.15:ProposalforinstallationafterorientationVEGAPULS69
The following table shows the necessary angle of inclination. It
depends on the measuring distance and the distance "a" between
vessel centre and installation position.
Distance d
(m)
2° 4° 6° 8° 10°
2 0.1 0.1 0.2 0.3 0.4
4 0.1 0.3 0.4 0.6 0.7
6 0.2 0.4 0.6 0.8 1.1
8 0.3 0.6 0.8 1.1 1.4
10 0.3 0.7 1.1 1.4 1.8
15 0.5 1 1.6 2.1 2.6
20 0.7 1.4 2.1 2.8 3.5
25 0.9 1.7 2.6 3.5 4.4
30 1 2.1 3.2 4.2 5.3
35 1.2 2.4 3.7 4.9 6.2
40 1.4 2.8 4.2 5.6 7.1
45 1.6 3.1 4.7 6.3 7.9
50 1.7 3.5 5.3 7 8.8
60 2.1 4.2 6.3 8.4 10.5
70 2.4 4.9 7.3 9.7 12.2