6 Set up with the display and adjustment module
VEGAPULS 69 • 4 … 20 mA/HART - two-wire
47247-EN-170315
In this menu item, the internal clock of the sensor is set to the request-
ed time and time format. At the time of shipment from factory, the
instrument is set to CET (Central European Time).
During a reset, the parameter settings carried out by the user are
reset to the default values (see below table).
Proceed as follows:
1. Select with [->] under "Additional adjustments" the menu item
"Reset"andconrmwith[OK].
2. Conrmwith[OK] and select the requested reset function with
[->]
3. Conrmwith[OK], for approx. 5 s the message "Resetting" is
displayed, then the selection window appears.
Caution:
For the duration of the reset, the set trouble signal is outputted via the
current output. Within the context of the asset management function,
the message "Maintenance" is outputted.
The following reset functions are available:
Delivery status: Restores the parameter settings at the time of ship-
mentfromthefactory,incl.theorder-specicsettings.Anycreated
falsesignalsuppression,user-programmablelinearizationcurveas
well as measured value and echo curve memory is deleted. The event
andparametermodicationmemoriesremainunaected.
Basic settings: Resets the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any stored
false signal suppression or user programmable linearisation curve, as
well as the measured value memory, is deleted. Order-related settings
are not taken over into the current parameters after this reset.
The following table shows the scope of the reset function and the
default values of the instrument:
Additional settings - Date/
Time
Additional adjustments
- Reset