User's Manual

Table Of Contents
54
6 Set up with the display and adjustment module
VEGAPULS 69 • 4 … 20 mA/HART - two-wire
47247-EN-170315
Menu Menu item Default value
Setup Measurement
loop name
Sensor
Units Distance in m
Temperature in °C
Application Medium: Crushed stones/gravel
Application: Silo
Vessel bottom: Flat
Vessel height/Measuring range: 120 m
Min. adjustment 120 m
Max. adjustment 0,000 m(d)
Damping 0.0 s
Current output
mode
Output characteristics: 4 … 20 mA
Failure mode: < 3.6 mA
Current output
Min./Max.
Min. current: 3.8 mA
Max. current: 20.5 mA
Display Displayed value 1 Filling height
Displayed value 2 Temperature
Backlight Switchedo
Additional adjust-
ments
Date/Time Time format: 24 h
Scalingsize Volume
l
Scaling format 100.00 lin %, 100 l
0.00 lin %, 0 l
Current output 1
and2size
Lin %
Current output 1
and 2 adjustment
100.00 %, 100 l
0.00 %, 0 l
Linearization Linear
HART mode HART address: 0
Loop current mode: Analogue cur-
rent output
The instrument settings are copied with this function. The following
functions are available:
Read from sensor: Read data from sensor and store into the display
and adjustment module
Write into sensor: Store data from the display and adjustment mod-
ule back into the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
All data of the menu "Setup" and "Display"
Additional settings - Copy
instrument settings