6 Set up with the display and adjustment module
VEGAPULS 69 • 4 … 20 mA/HART - two-wire
47247-EN-170315
In this menu item, you can read out the instrument name and the
instrument serial number:
In this menu item, the hardware and software version of the sensor is
displayed.
In this menu item, the date of factory calibration of the sensor as well
as the date of the last change of sensor parameters are displayed via
the display and adjustment module or via the PC.
In this menu item, the features of the sensor such as approval, pro-
cesstting,seal,measuringrange,electronics,housingandothers
are displayed.
6.6 Saving the parameterisation data
We recommended writing down the adjustment data, e.g. in this op-
erating instructions manual, and archiving them afterwards. They are
thus available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in menu item "Copydevice
settings" in the menu "Additional settings". The data remain there
permanently even if the sensor power supply fails.
The following data or settings for adjustment of the display and ad-
justment module are saved:
All data of the menu "Setup" and "Display"
Info - Instrument name
Info - Instrument version
Info - Factory calibration
date
Info - Sensor character-
istics
Backup on paper
Backup in the display and
adjustment module