6
2 For your safety
VEGAPULS 69 • 4 … 20 mA/HART - two-wire
47247-EN-170315
2.5 CE conformity
ThedevicefullsthelegalrequirementsoftheapplicableEUdirec-
tives.ByaxingtheCEmarking,weconrmtheconformityofthe
instrument with these directives.
YoucanndtheEUconformitydeclarationonourwebsiteunder
www.vega.com/downloads.
2.6 NAMUR recommendations
NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
acceptedasthestandardineldinstrumentation.
ThedevicefullstherequirementsofthefollowingNAMURrecom-
mendations:
•
NE 43 – Signal level for malfunction information from measuring
transducers
•
NE53–Compatibilityofelddevicesanddisplay/adjustment
components
•
NE107–Self-monitoringanddiagnosisofelddevices
For further information see www.namur.de.
2.7 Radio license for Europe
The instrument was tested according to the latest issues of the har-
monizedstandards:
•
EN 302372 - Tank Level Probing Radar
•
EN 302729 - Level Probing Radar
It is hence approved for use inside and outside closed vessels in
countries of the EU.
Use is also approved in EFTA countries, provided these standards
have been implemented.
For operation inside of closed vessels, the following conditions must
befullled:
•
The instrument must be permanently mounted on a closed vessel
made of metal, reinforced concrete, or comparable attenuating
materials
•
Flanges,processttingsandmountingaccessoriesmustensure
the microwave impermeability of the vessel and not let the radar
signal escape to the outside
•
If necessary, existing viewing windows in the vessel must be
coated with a microwave impermeable material (e.g. electrically
conductive coating)
•
Manholesandangesonthevesselmustbeclosedandsealedto
avoid penetration of the radar signal
•
The instrument should be preferably mounted on top of the vessel
with antenna orientation downward
For operation outside of closed vessels, the following conditions must
befullled: