9 Diagnosis, asset management and service
VEGAPULS 69 • 4 … 20 mA/HART - two-wire
47247-EN-170315
Fault description Error pattern Cause Rectication
2. Measured value
jumps towards 100 %
Level
time
0
Due to the process, the
amplitude of the product echo
decreases
A false signal suppression was
not carried out
Carry out a false signal suppres-
sion
Amplitude or position of a false
signal has changed (e.g. con-
densation, buildup); false signal
suppression no longer matches
actual conditions
Determine the reason for the
changed false signals, carry out
false signal suppression, e.g.
with condensation
Measurementerrorduringlling
Fault description Error pattern Cause Rectication
3. Measured value
jumps towards 0 %
duringlling
Level
Amplitude of a multiple echo
(vessel top - product surface) is
larger than the level echo
Check parameter "Application",
especially vessel top, type of
medium, dished bottom, high
dielectric constant, and adapt if
necessary
The level echo cannot be distin-
guished from the false signal at
a false signal position (jumps to
multiple echo)
Remove/reduce false signal:
minimizeinterferinginstallations
bychangingthepolarization
direction
Chose a more suitable installa-
tion position
Transversereectionfroman
extraction funnel, amplitude of
thetransversereectionlarger
than the level echo
Direct sensor to the opposite
funnel wall, avoid crossing with
thellingstream
4. Measured val-
ueuctuatesaround
10 … 20 %
Level
Various echoes from an uneven
product surface, e.g. a material
cone
Check parameter "Type of
medium" and adapt, if neces-
sary
Optimizeinstallationposition
and sensor orientation
Reectionsfromtheproduct
surface via the vessel wall
(deection)
Select a more suitable installa-
tionposition,optimizesensor
orientation, e.g. with a swivelling
holder
5. Measured value
jumps sporadically to
100%duringlling
Level
time
0
Changing condensation or con-
tamination on the antenna
Carry out a false signal suppres-
sion or increase false signal
suppression with condensation/
contamination in the close
range by editing
With bulk solids use radar sen-
sor with purging air connection
orexibleantennacover