4 Mounting
VEGAPULS 64 • 4 … 20 mA/HART - two-wire
51141-EN-160616
Socket diameter d Socket length h
50 mm ≤250mm
80 mm ≤300mm
100 mm ≤400mm
150 mm ≤500mm
Socket diameter d Socket length h
1½" ≤7.9in
2" ≤9.9in
3" ≤11.8in
4" ≤15.8in
6" ≤19.7in
The mounting socket should be as short as possible and its end
rounded. This reduces false echoes from the vessel mounting socket.
Fig. 16: Recommended socket mounting
Ifthemediumhasgoodreectiveproperties,youcanalsomountthe
VEGAPULS 64 on longer sockets. Approximate socket heights are
shown in the following illustration.
Information:
When mounting on longer sockets, we recommend carrying out a
false signal suppression (see chapter "Parameter adjustment").
d
h
The below charts specify the max. pipe socket length h depending on
the diameter d.
Socket diameter d Socket length h
80 mm ≤200mm
100 mm ≤300mm
Socketwithangecon-
nection