6.4 Setup procedure
In HART-Multidrop mode (several sensors on one input) the
address must be set before continuing with the parameter
adjustment. You will nd a detailed description in the operating
instructions manual of PLICSCOM or in the online help of
PACTware or DTM.
HART mode
Standard
Address 0
As VEGAPULS 62 is a distance measuring instrument, the
distance from the sensor to the product surface is measured.
To have the real product level displayed, an allocation of the
measured distance to the percentage height must be made. To
carry out this adjustment, the distance is entered with full and
empty vessel. If these values are not known, an adjustment
with the distance values, e.g. 10 % and 90 % is also possible.
Starting point for this distance specications is always the seal
surface of the thread or ange. With these settings the real
level is calculated. Furthermore the operating range of the
sensor is limited from maximum to the required range.
The real product level during this adjustment is not important,
because the min./max. adjustment is always carried out
without changing the product level. These settings can be
made ahead of time without the instrument having to be
installed.
In the main menu item "Basic adjustment", the individual
submenu items should be selected one after the other and
provided with the correct parameter values.
Start your parameter adjustment with the following menu items
of the basic adjustment:
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
Basic adjustment
Display
Diagnostics
Service
Info
Address setting HART-Multi-
drop
Parameter adjustment
Carrying out min. adjustment
Setup with the indicating and adjustment module PLICSCOM
VEGAPULS 62 - 4 ... 20 mA/HART 37