Medium
Liquid
According to the conductivity and the dielectric value of liquids,
the reection properties can dier considerably. Therefore
additional options such as "Solvent", "Chem. mixture" and
"Water based" are oered below the menu item Liquid.
With solids, you can choose between "Powder/Dust", "Gran-
ular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted
perfectly to the product and measurement reliability, partic-
ularly in products with bad reective properties, is considerably
increased.
Enter the requested parameter via the appropriate keys, save
your settings and jump to the next menu item with the [->] key.
Apart from the medium, the vessel shape can also inuence
the measurement. To adapt the sensor to the measuring
conditions, this menu item oers dierent options depending
on whether liquid or solid. With "Liquid" these are "Storage
tank", "Stilling tube", "Open vessel" or "Stirred vessel", with
"Solid", "Silo" or "Bunker".
Vessel form
Storage tank
Information:
With VEGAPULS 62 with electronics version "Increased
safety", "Solid" is preset as factory setting. However, the
instrument should be used preferably in liquids. In such cases,
the vessel form should be set to "Storage tank" during setup.
Enter the requested parameter via the appropriate keys, save
your settings and jump to the next menu item with the [->] key.
To suppress uctuation in the measured value display, e.g.
caused by a turbulent product surface, an integration time can
be set. This time can be between 0 and 999 seconds. Please
note that the reaction time of the entire measurement will be
longer and the sensor will react to quick changes of the
Vessel form
Damping
Setup with the indicating and adjustment module PLICSCOM
VEGAPULS 62 - 4 ... 20 mA/HART 39