User's Manual

Table Of Contents
l Displayed value
l Display unit
l Scaling
l Current output
l Units of measurement
l Language
The following safety-relevant data are not read out or written:
l HART mode
l PIN
l SIL
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following functions to the reset vales (see chart):
9)
Function Reset value
Max. adjustment 0 m(d)
Min. adjustment
30 m(d)(VEGAPULS 61 65)
35 m(d)(VEGAPULS 66)
70 m(d)(VEGAPULS 68)
Medium Liquid
Vessel form not known
Damping 0 s
Linearization Linear
Sensor-TAG Sensor
Displayed value Distance
Current output - characteristics 4 20 mA
Current output - max. current 20.0 mA
Current output - min. current 4 mA
Current output - failure <3.6 mA
Units of measurement m(d)
The values of the following functions are not reset to the reset
values (see chart) with "Reset":
9)
9)
Sensor-specic basic adjustment.
Setup with the indicating and adjustment module PLICSCOM
42 VEGAPULS 62 - 4 ... 20 mA/HART
28435-EN-060317