8 Maintenance and fault rectication
8.1 Maintenance
When used as directed in normal operation, VEGAPULS 62 is
completely maintenance-free.
8.2 Fault rectication
VEGAPULS 62 oers maximum reliability. Nevertheless faults
can occur during operation. These may be caused by the
following, e.g.:
l Sensor
l Process
l Supply
l Signal processing
The rst measures to be taken are to check the output signals
as well as to evaluate the error messages via the indicating
and adjustment module PLICSCOM. The procedure is
described below. Further comprehensive diagnostics can be
carried out on a laptop with the software PACTware and the
suitable DTM. In many cases, the causes can be determined in
this way and faults can be rectied.
Should the following measures not be successful, please call
in urgent cases the VEGA service hotline under the phone
number +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock.
Since we oer this service world-wide, the support is only
available in the English language. The service is free of
charge, only the standard telephone costs will be charged.
Connect a hand-held multimeter with a suitable measuring
range acc. to the wiring plan.
? 4 20 mA signal not stable
l level uctuations
à set integration time via PLICSCOM or PACTware
? 4 20 mA signal missing
l incorrect connection to power supply
à Check connection acc. to chapter "Connection proce-
dure" and correct, if necessary, acc. to chapter "Wiring
plans"
Causes of malfunction
Fault rectication
24 hour service hotline
Checking the 4 20 mA sig-
nal
Maintenance and fault rectication
50 VEGAPULS 62 - 4 ... 20 mA/HART