l No voltage supply
à check cables for line break, repair, if necessary
l supply voltage too low or load resistance too high
à check and adapt, if necessary
? Current signal greater than 22 mA or less than 3.6 mA
l Electronics defective
à Exchange instrument or return it for repair
In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
? E013
l no measured value available
à sensor in boot phase
à sensor does not nd an echo, e.g. because of faulty
installation or incorrect parameter adjustment
? E017
l Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E036
l No operable sensor software
à Carry out software update or send instrument for repair
? E041, E042, E043
l Hardware error, electronics defective
à Exchange instrument or return it for repair
8.3 Exchange of the electronics module
If the electronics module is defective, it can be replaced by the
user.
Error message via PLICSCOM
Maintenance and fault rectication
VEGAPULS 62 - 4 ... 20 mA/HART 51