User's Manual

Table Of Contents
Output variable
Output signal 4 20 mA/HART
Resolution 1.6 µA
Fault signal current output unchanged; 20.5 mA; 22 mA;
<3.6 mA (adjustable)
Current limitation 22 mA
Load see load diagram in Power supply
Integration time (63 % of the input
variable)
0 999 s, adjustable
Fullled NAMUR recommendation NE 43
Input variable
Parameter distance between process tting and product
surface
Min. distance from antenna end 50 mm (2 in)
Recommended meas. range depending on the antenna diameter
- ø 40 mm (1.6 in) up to 10 m (33 ft)
- ø 48 mm (1.9 in) up to 15 m (50 ft)
- ø 75 mm (3 in), ø 95 mm (3.7 in),
parabolic antenna
up to 30 m (98.4 ft)
Accuracy (similar to DIN EN 60770-1)
Reference conditions acc. to DIN EN 61298-1
- Temperature +18 +30°C (+64 +86°F)
- Relative humidity 45 75 %
- Atmospheric pressure 860 1060 mbar/86 106 kPa
(12.5 15.4 psi)
Supplement
56 VEGAPULS 62 - 4 ... 20 mA/HART
28435-EN-060317