912X-IS FISCO POWER
SUPPLIES
FSC-MBT
Termin ator
Relcom Inc.
4
5
6
7
8
3
1
2
POWER
Relcom Inc.
FCS-MB8-SG
POWER
FCS-MB4-SG
4
3
1
2
Relcom Inc.
Relcom Inc.
POWER
FCS-MB4-SG
4
3
1
2
Relcom Inc.
POWER
FCS-MB4-SG
4
3
1
2
Relcom Inc.
POWER
FCS-MB4-SG
4
3
1
2
Relcom Inc.
POWER
FCS-MB4-SG
4
3
1
2
Relcom Inc.
FSC-MBT
Termin ator
Relcom Inc.
FSC-MBT
Terminator
Safe or Zone/Division 2
hazardous area
9122-IS
FISCO power
supply, IIB
9121-IS
FISCO power
supply, IIC
AC power 85 - 265Vac
Zone/Division 1
hazardous area
IIC
IIB
8914-PS-AC
power
supply
8914-PS-AC
power
supply
Safe area
OVERVIEW
The 9121-IS and 9122-IS are fieldbus repeater isolators which repeat
the fieldbus signal from a safe area, Zone 2 or Division 2 fieldbus to
an intrinsically safe fieldbus for connection to devices in Zone or
Division 1. The 9121-IS provides up to 110mA, typically powering up
to 5 x 20mA field devices in Gas Group IIC and the 9122-IS provides
up to 250mA, typically powering up to 12 x 20mA field devices in
Gas Group IIB.
The 912x-IS is certified to FISCO (Fieldbus Intrinsically Safe COncept)
based on the Fieldbus FOUNDATION FF816-FISCO physical layer
profile and IEC/TS 60079-27 FISCO Technical Specification. This
allows the power supplied to the IS fieldbus to exceed the limit set in
the original FF-816 IS physical layer profile. This increases the number
of devices on an IS fieldbus from typically 4 x 20mA devices with
maximum of 80m cable run, to up to 12 x 20mA devices with 250m
cable run using the 9122-IS.
In addition, FISCO reduces the documentation required. Intrinsically
safe systems have been installed in accordance with IEC/EN60079-
14 or similar local code of practice. This requires:
calculation of cable parameters
comparison of safety descriptions
creation of descriptive system document
The administrative work involved in carrying this out in accordance
with the end users procedures is usually considerable. Simply adding a
new field device to an IS segment will require all this documentation to
be updated.
Fieldbus intrinsically safe systems can now also be installed in
accordance with IEC/TS 60079-27 FISCO Technical Specification.
This:
eliminates need to calculate cable parameters
reduces safety documentation to a list of devices
allows addition of devices without a review of safety
documentation
as proven by test, allows longer cables with higher
capacitance
To install a fieldbus system to IEC/TS 60079-27 FISCO Technical
Specification, the cable used in the system must comply with the
following parameters:
Loop resistance R
c
: 15 to 150 /km
Loop inductance L
c
: 0,4 to1 mH/km
Capacitance C
c
: 80 to 200 nF/km
Maximum length of each spur cable: 30 m in IIC and IIB
Maximum length of each trunk cable: 1 km in IIC 5 km in IIB
When cable which complies with this specification is used, no further
consideration of cable parameters is necessary. Virtually any
instrument cable suitable for a fieldbus signal will comply.
Alternatively if all these cable requirements are not met on a segment,
the FISCO power supplies can still be used in intrinsically safe systems,
calculating the cable parameters to IEC/EN60079-14 in the usual
way.