Operating Instructions Overvoltage arrester B62-30W Document ID: 40492 Separating and protective instruments
Contents Contents 1 About this document 1.1 1.2 1.3 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. .. .. 4 4 4 4 4 5 5 5 Structure . . . . . . . . . . . . . . . . . . Principle of operation . . . . . . . . . Packaging, transport and storage Installation in switching cabinet . . Mounting in housing . . . . . . . . . . . . . . . . . . . . . .
1 About this document 1 About this document 1.1 Function This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device. 1.2 Target group This operating instructions manual is directed to trained qualified personnel.
2 For your safety 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use The B62-30W is an overvoltage arrester for supply and control cables for Profibus PA instruments.
2 For your safety 2.6 CE conformity This device fulfills the legal requirements of the applicable EC guidelines. By attaching the CE mark, VEGA provides a confirmation of successful testing. You can find the CE conformity declaration in the download area of www.vega.com. 2.7 Safety instructions for Ex areas Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.
3 Product description 3 Product description 3.1 Structure Scope of delivery The scope of delivery encompasses: l l Constituent parts Overvoltage arrester B62-30W Documentation - this operating instructions manual - Ex specific safety instructions and, if necessary, further certificates The following illustration shows the configuration of the overvoltage arrester B62-30W: OUT A1 A2 B62 - 30 W A1+ A2- 2 Ri = 3,6 Ohm max. 36 VDC/ li 0,4 A IP 20 4 E1+ E2- 1 3 E1 E2 IN Fig.
3 Product description 3.2 Principle of operation Application area Voltage surges can be caused by indirect atmospheric discharges (lightning strokes) or switching operations in the supply network. Further causes can be inductive or capacitive couplings from other electrical systems. Voltage peaks (transients) must be expected especially when long power supply and signal cables are used. Such voltage surges can cause damage to sensors and signal conditioning instruments.
3 Product description Storage and transport temperature l l l l l Not in the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration l Storage and transport temperature see chapter "Supplement Technical data - Ambient conditions" Relative humidity 20 … 85 % l 40492-EN-110527 8 Overvoltage arrester • B62-30W
3 Product description 3.4 Installation in switching cabinet The overvoltage arrester is mounted in the switching cabinet on carrier rails according to EN 50 022 (DIN rail) or EN 50 035 (C-rail). It is fastened to the carrier rail with a screw located on its exterior. The screw is marked with the symbol for functional ground. Depending on the version, it may be galvanically connected to the ground terminal of the overvoltage arrester (see circuit diagram in chapter "Wiring plan").
3 Product description 1 Loosen fixing screw OUT 1 IP 20 IN Fig. 4: Mounting on carrier rail 1 Fixing screw 2 Place the overvoltage arrester onto the rail and let it snap in 3 Tighten fixing screw 3.5 Mounting in housing The overvoltage arrester is optionally available in a plastic or aluminium housing. Make sure when mounting that the cable glands point downward. Thus avoids water ingress. 1 OUT IP 20 IN 2 3 Fig.
3 Product description 1 OUT IP 20 IN 2 3 Fig. 6: Mounting in plastic housing 1 2 3 Overvoltage arrester Pressure compensation Ground terminal 40492-EN-110527 The carrier rail inside the housing is galvanically connected to the ground terminal outside on the housing. This ground terminal must be connected (low impedance) with the potential equalization line (PA). The wire cross-section must be at least 2.5 mm2, the cable must be as short as possible.
4 Connecting to power supply 4 Connecting to power supply 4.1 Preparing the connection Note safety instructions Always keep in mind the following safety instructions: l Connect only in the complete absence of line voltage Before starting setup make sure that the power supply corresponds to the specifications on the type label. For effective overvoltage protection, the cables between overvoltage arrester and instrument should be as short as possible.
4 Connecting to power supply 4.3 Wiring plan Circuit diagram E1 A1 E2 A2 1 2 Fig. 7: Circuit diagram B62-30W 1 2 Circuit diagram overvoltage arrester B62-30W Potential equalisation Wiring plan 2 3 + - OUT A1 A2 E1 E2 B62 - 30 W A1+ A2- 1 1+ 2- Ri = 3,6 Ohm max. 36 VDC/ li 0,4 A IP 20 E1+ E2- IN 4 Fig.
5 Maintenance and fault rectification 5 Maintenance and fault rectification 5.1 Maintenance If the device is used properly, no special maintenance is required in normal operation. 5.2 Fault rectification Reaction when malfunctions occur The operator of the system is responsible for taking suitable measures to remove interferences. Fault rectification The first measure to be taken is to check the input/output signal as well as the power supply.
6 Dismounting 6 Dismounting 6.1 Dismounting steps Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. 6.2 Disposal The device consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable. WEEE directive 2002/96/EG This device is not subject to the WEEE directive 2002/96/EG and the respective national laws.
7 Supplement 7 Supplement 7.1 Technical data General data Version Device for carrier rail mounting Housing material Plastic (PPE) Weight approx. 175 g (0.385 lbs) Electrical characteristics1) Nominal supply voltage 9 … 36 V DC Max. permissible current per circuit 0.6 A Ri per circuit < 3.6 Ω Li per circuit = 0 mH Ri per circuit = 2.
7 Supplement 7.2 Dimensions B62-30W 84 mm (3.31") Overvoltage arrester 52 mm (2.05") 25 mm (0.98") 40492-EN-110527 Fig.
7 Supplement Housing 50 mm (1.97") 120 mm (4.72") 86 mm (3.39") m m ,5 8") ø4 0.1 ( 47 mm (1.85") 77 mm (3.03") M 20 x 1,5 160 mm (6.30") 1 72 mm (2.84") 82 mm (3.23") m m ,5 2") ø5 0.2 ( 68 mm (2.68") 130 mm (5.12") 116 mm (4.57") M 20 x 1,5 2 Fig.
40492-EN-110527 7 Supplement Overvoltage arrester • B62-30W 19
Printing date: VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info@de.vega.com www.vega.com ISO 9001 All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information available at the time of printing.