Owner's manual

1
2
3
OUT
IN
IP 20
Fig. 6: Mounting
in plastic housing
1 Overvoltage arrester
2 Pressure compensation
3 Ground terminal
The carrier rail inside the housing is galvanically connected to the
ground terminal outside on the housing. This ground terminal must be
connected (low impedance) with the potential equalization line (PA).
The wire cross-section must be at least 2.5 mm
2
, the cable must be as
short as possible.
Overv
oltage arrester B62-30W 11
3 Produc
t description
40492-EN-110527