6Setupwiththedisplayandadjustmentmodule
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
The implementation of a real value corretion is only necessary if the
requirementsofthemeasurementloophavechanged,forexample
withabrasioninatube.
Ifyouknowthedensityofacertainmedium,youcanenterthedeter-
mined real density in this menu item to correct the measured value.
Thefunctionshiftsthelinearizationcurvetothisdeterminedpoint.
The measurement can thus be adapted exactly to the conditions in
the tube.
In this menu item you can activate the relay output and determine its
functionaswellastheswitchingpoints.
When the output of the process values is set, you can choose be-
tweenoverllanddryrunprotection.
The relay outputs of the sensor react accordingly.
Thefollowingreferencevaluescanbeselected:
•
None - Relay operates as fail safe relay
•
Electronics temperature
•
Process value
"No" reference value means that the relay output operates as fail safe
relay.
Push the [->] button, to reach the relay settings.
Example for the adjustment of the process value
Firstofallselecttherequestedmode(overllordryrunprotection).
Caution:
Independentoftheselectedreferencevalue,therelaywilldeenergize
in case of failure.
With this menu item you safeguard the sensor parameters against
unauthorizedorunintentionalmodications.
This menu item is described in the operating instructions manual
"Display and adjustment module".
Setup - Real value correc-
tion (manually)
Setup - Relay
Lock setup - adjustment