6Setupwiththedisplayandadjustmentmodule
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
Default settings: Resetting of the parameter adjustment like under
"Basic settings". In addition, special parameters are reset to default
values.Order-specicsettingsaredeleted.
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item "Setup" to the default values of the respective
instrument.Order-specicsettingsremainbutarenottakenoverinto
the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
Thefollowingtableshowsthedefaultvaluesoftheinstrument.The
values apply for the application "Level". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
availableortheymaybedierentlyassigned:
Menu Menu item Default value
Setup Measurement loop name Sensor
Isotope Cs-137
Application Density
Background radiation 0 ct/s
Unit of the process value g/cm
3
Temperature unit ° C
Adjustment min. process
value
0.500 g/cm
3
Adjustment max. process
value
1.500 g/cm
3
Inner diameter 0.20 m
Linearization 90000 ct/s and 0.500 g/cm
3
Damping 60 s
Real value correction 0
Reference value - Relay None
Block adjustment Released
Display Language Selected language
Displayed value Pulse rate
Display unit ct/s
With this function
Load parameter adjustment data from the sensor into the display
and adjustment module
Write parameter adjustment data from the display and adjustment
module into the sensor
This parameter is described in the operating instructions manual
"Display and adjustment module".
Additional adjustments -
Copy instrument settings