6Setupwiththedisplayandadjustmentmodule
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
StartwiththesetupofMINITRAC31.
In the main menu point "Setup", the individual submenu points
shouldbeselectedoneaftertheotherandprovidedwiththecorrect
parameters to ensure optimum adjustment of the measurement. The
procedureisdescribedinthefollowing.
Stickwiththenormalsequenceofthemenuitemsascloselyaspos-
sible.
Setup
In this menu item you can adjust the MINITRAC 31 to the integrated
isotope in the source container.
Forthispurpose,checkwhichisotopeisintegratedinthesource
container.Youcanndthisinformationonthetypelabelofthesource
container.
Through this selection, the sensitivity of the sensor is adapted
perfectly to the isotope. The normal reduction of the emitter activity is
hence considered through the radioactive decay.
TheMINITRAC31requiresthisinformationoftheautomaticdecay
compensation. This ensures an interference-free measurement over
the complete life time of the gamma emitter - an annual recalibration
is not necessary.
Entertherequestedparametersviatheappropriatekeys,saveyour
settingswith[OK]andjumptothenextmenuitemwiththe[ESC] and
the [->] key.
Enter here, the respective application.
Thismenuitemenablesadaptationofthesensortotherequestedap-
plication.Youcanchoosebetweenthefollowingapplications:"Level",
"Point level" or "Summation Slave".
Thenaturalradiationonearthinuencestheaccuracyofthemeas-
urement.
With this menu item the natural background radiation can be faded
out.
For this purpose, the MINITRAC 31 measures the natural background
radiationandsetsthepulseratetozero.
Setup - Isotope
Setup - Application
Setup - Background
radiation