6Setupwiththedisplayandadjustmentmodule
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
With this menu item you safeguard the sensor parameters against
unauthorizedorunintentionalmodications.
This menu item is described in the operating instructions manual
"Display and adjustment module".
Display
With this parameter you can change the display language.
This parameter is described in the operating instructions manual
"Display and adjustment module".
With this parameter you can change the indication of the display.
Youcanchooseifthedisplayshouldshowtheactualpulserateorthe
electronics temperature.
Diagnostics
Inthismenuitem,youcanenquirethestatusofyoursensor.Innormal
operation, the sensor displays the message "OK". In case of fault, you
willndthecorrespondingfaultcodehere.
This parameter is described in the operating instructions manual
"Display and adjustment module".
The peak value function holds the max. and min. values during opera-
tion.
This parameter is described in the operating instructions manual
"Display and adjustment module".
Here, you can retrieve the adjustment value of the sensor. This is the
percentagevalueofthemax.pulserateatwhichthesensorswitches
over.
If you have carried out a single point adjustment, this is the entered
value.Withatwo-pointadjustment,thisisthecalculatedvalue.
The value is an indication for the reliability and reproducibility of the
switchingpoint.
Thegreaterthedierenceinthepulseratebetweencoveredand
uncoveredstatus,thegreaterthedierentialvalue(DeltaI)andthe
more reliable the measurement. The automatically calculated damp-
ing is also oriented around the Delta I value. The higher the value, the
lowerthedamping.
ADeltaIvaluebelow10%isanindicationforacriticalmeasurement.
Lock setup - adjustment
Display - Language
Display/Displayed value
Diagnostics - Device
status
Diagnosis - Peak value
Diagnosis - Adjustment
data