User guide

58
6Setupwiththedisplayandadjustmentmodule
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
Enter here, the respective application.
Thismenuitemenablesadaptationofthesensortotherequestedap-
plication.Youcanchoosebetweenthefollowingapplications:"Level",
"Density", "Limit level", "X-ray alarm" or "Real value correction".
With this menu item you safeguard the sensor parameters against
unauthorizedorunintentionalmodications.
This menu item is described in the operating instructions manual
"Display and adjustment module".
6.8 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructionsmanual,andarchivingthemafterwards.Theyarethus
available for multiple use or service purposes.
Iftheinstrumentisequippedwithadisplayandadjustmentmodule,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in the operating instructions
manual "Display and adjustment module" in the menu item "Copy
sensor data". The data remain there permanently even if the sensor
powersupplyfails.
Thefollowingdataorsettingsforadjustmentofthedisplayandad-
justment module are saved:
All data of the menu "Setup" and "Display"
In the menu "Additional adjustments" the items "Sensor-specic
units, temperature unit and linearization"
Thevaluesoftheuserprogrammablelinearizationcurve
The function can also be used to transfer settings from one instru-
ment to another instrument of the same type. If it is necessary to
exchange a sensor, the display and adjustment module is inserted
intothereplacementinstrumentandthedataarelikewisewritteninto
the sensor via the menu item "Copy sensor data".
Setup - Application
Lock setup - adjustment