9 Diagnostics and service
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
Code
Text mes-
sage
Cause Rectication
S017
Accuracy
outside the
specication
– Accuracy outside the
specication
– Correct adjustment data
S025
Badlineariza-
tion table
– Badlinearizationtable – Carryoutlinearization
S038
Slave outside
thespecica-
tion
– Slaveoutsidethespecica-
tion
– Check Slave
S125
Ambient tem-
perature too
high/toolow
– Ambient temperature too
high/toolow
– Protectinstrumentwith
isolating material against
extreme temperatures
The instrument has no status messages to the section "Maintenance".
9.3 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
Therstmeasuresare:
•
Evaluation of fault messages via the indicating and adjustment
module
•
Checking the output signal
•
Treatment of measurement errors
FurthercomprehensivediagnosispossibilitiesareoeredbyaPC
withthesoftwarePACTwareandsuitableDTM.
In many case, the failure reasons can thus be determined and faults
rectied.
Thefollowingtabledescribespossibleerrorswiththeoutputsignal
and helps to remove them:
Error Cause Rectication
Output signal not stable Leveluctuations Set damping according to the instrument via
the display and adjustment module or PACT-
ware/DTM
Output signal missing Electrical connection faulty Check connection according to chapter
"Connection steps" and if necessary, correct ac-
cording to chapter "Wiring plan"
Voltagesupplymissing Check cables for breaks; repair if necessary
Operatingvoltagetoolow Check, adapt if necessary
Maintenance
Reaction when malfunc-
tions occur
Procedure for fault recti-
cation
Check output signal
(level measurement)