User guide
75
11 Supplement
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
Revisions Data DD-Revision Rev_01
CFF-File 010101.c
Device Revision 0101.o
0101.sym
C-Revision xx xx 01
Devicesoftwarerevision > 1.5.0
ITK (Interoperability Test Kit) Number 6.0.1
Electricial Characteristics Physicial Layer Type Low-powersignaling,bus-pow-
ered, FISCO I.S.
Input Impedance >3000Ohmsbetween7.8KHz-
39KHz
Unbalanced Capacitance < 250 pF to ground from either in-
put terminal
Output Amplitude 0.8VP-P
Electrical Connection 4 Wire
Polarity Insensitive Yes
Max. Current Load 10 mA
Device minimum operating voltage 9V
Transmitter Function Blocks Resource Block (RB) 1
Transducer Block (TB) 1
Standard Block (AI) 3
Execution Time 30 ms
Diagnostics Standard Yes
Advanced Yes
Performance No
Function Blocks Instantiable No
General Information LAS (Link Active Scheduler) No
Master Capable No
NumberofVCRs(VirtualCommunication
Relationships)
24
Function block Analog Input (AI)
The function block "Analog Input (AI)" takes the original measured value selected by a Channel
Number and makes it available to additional function blocks on its output.