User guide
78
11 Supplement
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
FF descriptor Rel. In-
dex
Description Unit
POINT_LEVEL_AD-
JUST_MODE
54 Point level adjustment mode -
RELAY_VALUE_SEL 55 Relay basic value -
DIGITAL_IN 56 Frequencyofdigitalinput -
DIGITAL_IN_BOOL 57 State of digital input -
ANALOG_IN 58 Current on analog input -
FF_CHANNEL_AVAIL-
ABLE
59 Available channels -
FF_CHANNEL_USED 60 Used channels -
Mapping of Process Value Status
Hex Quality Sub-Status Condition
0x00 Bad Non-specic Unexpected error
0x01 Bad CongurationError ItwastriedtosetawrongunitwithFFinterface
On user error codes: 16, 17, 25, 52, 57, 66, 72,
117, 120
0x0C Bad Device Failure Five or more internal communications have failed
while"ProcessDataUpdate".Lastusablevalueis
displayed
On user error codes: 8, 34, 35, 36, 37, 38, 73, 80,
86, 121, 122, 141
0x10 Bad Sensor Failure On user error codes: 40, 41, 53, 68, 123, 124, 125
0x1C Bad Out of Service Transducer block is in mode "Out of Service"
Channel is not assigned to an AIFB
Channel is not available in running application
0x20 Bad Transducer in MAN Transducer block is in mode "Manual"
0x44 Uncertain LastUsableValue Three or more internal communications have failed
while"ProcessDataUpdate".Lastusablevalueis
displayed
0x48 Uncertain Substitute On user error codes: 29
0x4C Uncertain InitialValue After startup of device or channel assignment in
AIFBwaschanged.Thechannelunitmaybeun-
knownuntilnext"ProcessDataUpdate"
On user error codes: 13
0x80 Good (NC) Non-specic No errors concerning to channel handling
On user error codes: 0, 33, 45, 71, 126, 127
Mapping of User Error Codes to FF Field Diagnostics
Priority Description User Error Codes NE-107 Status
31 Hardwarefailure 40, 41 FAILURE
30 Memory failure 34, 35, 36, 37 FAILURE