1 Function as Modbus-TCP server
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
Status Measured
value
Meaning
<> 0 0 An error number is transmitted in the status
corresponding to the error codes Exx (e.g. 29
= E29 = Simulation).
<> 0 XX0XX An error number which corresponds to the er-
ror codes Exx is transmitted in the status and
in the measured value. Must be congured
via DTM.
The switching conditions of the relay are transferred as bit information.
The following equivalencies apply to the switching relays:
0 = Switching status O
1 = Switching status On
The following equivalencies apply to the fail safe relay:
0 = Failure message O, relay switching condition On
1 = Failure message O, relay switching condition O
The following chart shows the addressing of the temporary memory
via Modbus.
Register ad-
dress in
Modicon
Temporary memory of VE-
GAMET/PLICSRADIO (1 bit)
Temporary memory of VE-
GAMET 391 (1 Bit)
10001 Fail safe relay Fail safe LED
10002 Relay 1 Relay 1
10003 Relay 2 Relay 2
10004 Relay 3 Relay 3
10005 ---- Relay 4
10006 ---- Relay 5
10007 ---- Relay 6
As an alternative, register address 00001 is also available as start
address.
Filing of the relay values