User guide
8
1 Function as Modbus-TCP server
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
Status Measured
value
Meaning
<> 0 0 An error number is transmitted in the status
corresponding to the error codes Exx (e.g. 29
= E29 = Simulation).
<> 0 XX0XX An error number which corresponds to the er-
ror codes Exx is transmitted in the status and
in the measured value. Must be congured
via DTM.
The switching conditions of the relay are transferred as bit information.
The following equivalencies apply to the switching relays:
•
0 = Switching status O
•
1 = Switching status On
The following equivalencies apply to the fail safe relay:
•
0 = Failure message O, relay switching condition On
•
1 = Failure message O, relay switching condition O
The following chart shows the addressing of the temporary memory
via Modbus.
Register ad-
dress in
Modicon
Temporary memory of VE-
GAMET/PLICSRADIO (1 bit)
Temporary memory of VE-
GAMET 391 (1 Bit)
10001 Fail safe relay Fail safe LED
10002 Relay 1 Relay 1
10003 Relay 2 Relay 2
10004 Relay 3 Relay 3
10005 ---- Relay 4
10006 ---- Relay 5
10007 ---- Relay 6
As an alternative, register address 00001 is also available as start
address.
Filing of the relay values