Manual

10 VEGACOM 557 - without protocol
Technical data
Electrical protective measures
Protection:
not mounted IP 00
in carrier BGT 596
or BGT LOG 571
- front side completely equipped IP 40
- upper and lower side
BGT 596 IP 00
BGT LOG 571 IP 20
- wiring side IP 00
in housing type 505
- front side IP 40
- other sides IP 30
Protection class II (in housing type 505)
Overvoltage category II
Electrical separating measures
Reliable separation acc. to VDE 0106, part 1 between power supply, LOGBUS, DIS-
BUS, PC-connection and appropriate interface
- reference voltage 250 V
- test voltage 2 kV
CE-approval, conformity judgement
VEGACOM 557 meets the protective regulations of EMVG (89/336/EWG) and NSR (73/23/
EWG). The conformity has been judged acc. to the following standards:
EMVG Emission EN 50 081 - 1: 1993
Susceptibility EN 50 082 - 2: 1995
NSR EN 61 010 - 1: 1993
Ambient conditions
Permissible ambient temperature -20°C +60°C
Storage and transport temperature -20°C … +85°C
Humidity 93 %, T = 40°C acc. to DIN/IEC 68-2-3
Shock load 2 … 100 Hz, 0,7 g
Mechanical data
Series module unit for
- carrier BGT 596
- carrier BGT LOG 571
- housing type 505
Dimensions, unassembled W = 25,4 mm (5 TE), H = 128,4 mm, D = 166 mm
Weight approx. 550 g