Manual

VEGACOM 557 - without protocol 9
Technical data
4 Technical data
Power supply
Operating voltage U
nom
= 24 V AC (20 … 53 V), 50/60 Hz or
= 24 V DC (20 … 72 V)
Power consumption approx. 6 VA
Fuse 1 A, slow-blow
Electrical connection
Component multiple plug acc. to DIN 41 612, series F
48-pole (d, b, z) with coding holes
Module in carrier
BGT 596 or BGT LOG 571 suitable multipoint connector acc. to DIN 41 612
with connection via standard technologies
Housing type 505 via screw terminals max. 1 x 1,5 mm
2
Indicating elements
LED in front plate green BA: without function
red (flashing): DISBUS/LOGBUS-failure
red (flashing irregularly): no PC/PLC-outputs
co-ordinated to the measurement loop
red (permanently): failure
green on: operating voltage on
Meas. data input DISBUS
Data transmission DISBUS (digital data transmission)
Connection line 2-wire standard line (screening recommended)
Line length max. 1000 m
Meas. data input LOGBUS
Data transmission LOGBUS (digital data transmission)
Connection line connection via BUS-plug
PC-interface
Interface standard RS 232 C
Line length max. 15 m
Transmission rate in baud
1)
300, 600, 1200, 2400, 4800, 9600, 19200, 38400
Transmission format
1)
8 data bits, 1 Stop bit, no parity or even parity
Plug in the front plate SUB-D-plug connector, 9-pole, pins
1)
via DIL-switch adjustable on the basic board