Operating Instructions Vibrating level switch for liquids VEGASWING 61 - transistor (NPN/PNP) Document ID: 29225
Contents Contents About this document 1.1 Function............................................................................................................................ 4 1.2 Target group...................................................................................................................... 4 1.3 Symbolism used................................................................................................................ 4 2 For your safety 2.1 Authorised personnel....................
Contents Supplementary documentation Information: Supplementary documents appropriate to the ordered version come with the delivery. You can find them listed in chapter "Product description". 29225-EN-130409 Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your VEGASWING 61, we offer accessories and replacement parts.
1 About this document 1 About this document 1.1 Function 1.2 Target group 1.3 Symbolism used This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device. This operating instructions manual is directed to trained qualified personnel.
2 For your safety 2 2.1 For your safety Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use The VEGASWING 61 is a sensor for level detection. You can find detailed information on the application range in chapter "Product description".
2 For your safety successful testing. You can find the CE conformity declaration in the download area of "www.vega.com". 2.7 SIL conformity 2.8 Safety instructions for Ex areas 2.9 Manufacturer declaration for zone 2 VEGASWING 61 fulfills the requirements of functional safety according to IEC 61508 resp. IEC 61511. You can find further information in the Safety Manual "VEGASWING series 60". Please note the Ex-specific safety information for installation and operation in Ex areas.
3 Product description 3 Product description 3.
3 Product description Application area 3.2 Principle of operation VEGASWING 61 is a point level sensor with tuning fork for level detection. It is designed for industrial use in all areas of process technology and can be used in liquids. Typical applications are overfill and dry run protection. With its tuning fork of only 40 mm length, VEGASWING 61 can also be mounted e.g. in pipelines from DN 32. The small tuning fork allows use in vessels, tanks and pipes.
3 Product description • Packaging Mode adjustment for selection of the switching condition (A/B) 3.4 Storage and transport Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180. The packaging of standard instruments consists of environmentfriendly, recyclable cardboard. The sensor is also equipped with a protective cap of ABS. For special versions, PE foam or PE foil is also used.
4 Mounting 4 Mounting 4.1 General instructions Suitability for the process Make sure that all parts of the instrument coming in direct contact with conditions the process, especially the sensor element, process seal and process fitting and suspension cable, are suitable for the existing process conditions, such as process pressure, process temperature as well as the chemical properties of the medium. You can find the specifications in chapter "Technical data" and on the type plate.
4 Mounting 1 Fig. 3: Mounting horizontal 1 Switching point 2 1 Fig. 4: Horizontal installation (recommended mounting position, particularly for adhesive products) 1 2 Switching point Marking with screwed version on top, with flange versions directed to the flange holes With flange versions, the fork is directed as follows to the flange holes. Fig. 5: Fork position with flange versions Moisture Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland.
4 Mounting Fig. 6: Measures against moisture penetration Transport Caution: Do not hold VEGASWING 61 on the tuning fork. Particularly with flange or tube versions, the tuning fork can be damaged just by the weight of the instrument. Transport coated instruments very carefully and avoid touching the tuning fork. Remove the packaging or the protective cover just before installation. Pressure/Vacuum The process fitting must be sealed if there is gauge or low pressure in the vessel.
4 Mounting 1 Fig. 7: Marking on the welded socket 1 Adhesive products Marking In case of horizontal mounting in adhesive and viscous products, the surfaces of the tuning fork should be vertical in order to reduce buildup on the tuning fork. On the screwed version you will find a marking on the hexagon. With this, you can check the position of the tuning fork when screwing it in. When the hexagon touches the seal, the thread can still be turned by approx. half a turn.
5 Connecting to power supply 5 Note safety instructions Take note of safety instructions for Ex applications Voltage supply Connecting to power supply 5.1 Preparing the connection Always keep in mind the following safety instructions: • Connect only in the complete absence of line voltage In hazardous areas you must take note of the respective regulations, conformity and type approval certificates of the sensors and power supply units.
5 Connecting to power supply 8. Check the hold of the wires in the terminals by lightly pulling on them 9. Tighten the compression nut of the cable entry. The seal ring must completely encircle the cable 10. Screw the housing cover back on The electrical connection is hence finished. 5.3 Housing overview Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the Ex-d version. 4 4 1 4 2 3 Fig.
5 Connecting to power supply Wiring plan We recommend connecting VEGASWING 61 in such a way that the switching circuit is open when there is a level signal, line break or failure (safe condition). The instrument is used to control relays, contactors, magnet valves, warning lights, horns as well as PLC inputs. Caution: There is no reverse polarity protection. Take note of the polarity of the output lines. - + 1 2 3 4 + - Fig. 10: NPN action - + 1 2 3 4 + - Fig.
6 Setup 6 Setup 6.1 General information The figures in brackets refer to the following illustrations. Function/Configuration With plastic housings, the switching condition of the electronics can be checked when the housing cover is closed (control lamp). With the basic setting, products with a density > 0.7 g/cm³ (0.025 lbs/in³) can be detected. For products with lower density, the switch must be set to > 0.5 g/cm³ (0.018 lbs/in³).
6 Setup "Function chart" (A - max. detection or overflow protection, B - min. detection or dry run protection). Sensitivity adjustment (3) With this DIL switch (3) you can set the switching point to liquids having a density between 0.5 and 0.7 g/cm³ (0.018 and 0.025 lbs/ in³). With the basic setting, liquids with a density of > 0.7 g/cm³ (0.025 lbs/in³) can be detected. In liquids with lower density, you must set the switch to > 0.5 g/cm³ (0.018 lbs/in³).
6 Setup Level Failure any Switching status Control lamp open 29225-EN-130409 flashes red VEGASWING 61 • - transistor (NPN/PNP) 19
7 Maintenance and fault rectification 7 Maintenance and fault rectification 7.1 Maintenance 7.2 Rectify faults If the instrument is used properly, no special maintenance is required in normal operation. Reaction when malfunctions occur The operator of the system is responsible for taking suitable measures to rectify faults. Failure reasons VEGASWING 61 offers maximum reliability. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.
7 Maintenance and fault rectification Checking the switching signal Error Cause VEGASWING 61 signals Operating voltage too "covered" without being low submerged (overfill proElectronics defective tection) VEGASWING 61 signals "uncovered" when being submerged (dry run protection) Rectification Check operating voltage Press the mode switch. If the instrument then changes the mode, the vibrating element may be covered with buildup or mechanically damaged.
7 Maintenance and fault rectification You find all information to the electronics exchange in the operating instructions of the new electronics module. In general, all electronics modules of series SW60 can be interchanged. If you want to use an electronics module with a different signal output, you carry out the complete setup. You find the necessary, suitable operating instruction on our homepage. Note: Keep in mind that enamelled instrument versions need special electronics modules.
8 Dismounting 8 8.1 Dismounting Dismounting steps Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present. 8.
9 Supplement 9 Supplement 9.1 Technical data General data Material 316L corresponds to 1.4404 or 1.4435 Materials, wetted parts ƲƲ Process fitting - thread 316L, Hastelloy C22 (2.4602) ƲƲ Process seal Klingersil C-4400 ƲƲ Process fitting - flange ƲƲ Tuning fork ƲƲ Extension tube: ø 21.3 mm (0.839 in) Materials, non-wetted parts 316L, 316L with Hastelloy C22 plated, 316L with ECTFE coated, 316L with PFA coating 316L, Hastelloy C22 (2.4602) 316L, Hastelloy C22 (2.
9 Supplement ƲƲ Standard Ra 3 µm (1.18-4 in) ƲƲ Hygienic version (3A) Ra < 0.3 µm (1.18-5 in) ƲƲ Hygienic version (3A) Process fittings Ra < 0.8 µm (3.15-5 in) ƲƲ Pipe thread, cylindrical (DIN 3852-A) G¾, G1 A ƲƲ Flanges DIN from DN 25, ANSI from 1" ƲƲ American pipe thread, conical (ASME B1.20.1) ƲƲ hygienic fittings Max.
9 Supplement Influence of the process temperature on the switching point 1 4 10 ( 25/64") 8 ( 5/16") 6 ( 15/64") 4 ( 5/32") 3 2 ( 5/64") 0 2 -2 (-5/64") -4 (-5/32") -6 (-15/64") -8 (-5/16") -10 (-25/64") 50 °C (122 °F) 0 °C (32 °F) 100 °C (212 °F) 150 °C (302 °F) 200 °C (392 °F) 250 °C (482 °F) Fig.
9 Supplement Influence of the process pressure to the switching point 1 4 10 ( 25/64") 8 ( 5/16") 6 ( 15/64") 4 ( 5/32") 3 2 ( 5/64") 0 2 -2 (-5/64") -4 (-5/32") -6 (-15/64") -8 (-5/16") -10 (-25/64") 12 (174,1) 25 (362,6) 38 (551,1) 51 (739,7) 64 (928,2) Fig. 26: Influence of the process pressure to the switching point 1 2 3 4 Shifting of the switching point in mm (in) Process pressure in bar (psig) Switching point at reference conditions (notch) Tuning fork Repeatability 0.1 mm (0.
9 Supplement VEGASWING 61 of 316L/Hastelloy C4 (2.
9 Supplement 1 64 (928) 40 (580) 20 (290) -1 (-14,5) -50 °C (-58 °F) 0 °C (32 °F) 50 °C (122 °F) 100 °C (212 °F) 150 °C (302 °F) 200 °C (392 °F) 250 °C (482 °F) 2 Fig. 29: Process temperature - Process pressure with switch position 0.5 g/cm³ (sensitivity switch) 1 2 Process pressure in bar (psig) Process temperature in °C (°F) Viscosity - dynamic 0.1 … 10000 mPa s (requirement: with density 1) Density 0.7 … 2.5 g/cm³ (0.025 … 0.09 lbs/in³); 0.5 … 2.5 g/cm³ (0.018 … 0.
9 Supplement ƲƲ Colour - standard PE Black ƲƲ Colour - Ex-version Blue ƲƲ Colour - standard PUR Adjustment elements Mode switch ƲƲ A ƲƲ B Density changeover switch ƲƲ 0.5 ƲƲ 0.7 Voltage supply Operating voltage Power consumption Electrical protective measures Protection rating Blue Max. detection or overflow/overfill protection Min. detection or dry run protection 0.5 … 2.5 g/cm³ (0.018 … 0.9 oz/in³) 0.7 … 2.5 g/cm³ (0.025 … 0.9 oz/in³) 10 … 55 V DC max. 0.
9 Supplement 9.2 Dimensions Housing in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar ~ 69 mm (2.72") ø 79 mm (3.11") 1 M20x1,5/ ½ NPT ø 86 mm (3.39") 116 mm (4.57") 112 mm (4.41") 112 mm (4.41") M20x1,5/ ½ NPT ~ 116 mm (4.57") 117 mm (4.61") ~ 59 mm (2.32") ø 80 mm (3.15") ~ 69 mm (2.72") ø 79 mm (3.03") M20x1,5 M20x1,5/ ½ NPT M20x1,5/ ½ NPT 2 3 4 Fig. 30: Housing versions in protection IP 66/IP 67 and IP 66/IP 68; 0.
9 Supplement 57 mm (2.24") 36 mm (1.42") 2 55 mm (2.17") 1 53 mm (2.09") 32 (G¾A, ¾"NPT) 41 (G1A, 1"NPT) G¾A, ¾"NPT G1A, 1"NPT 6 3 5 49 mm (1.93") 4 50 mm (1.97") ø 33,7 mm (1.33") 53 mm (2.09") 53 mm (2.09") 50 mm (1.97") 19 mm (0.75") G¾=66 mm (2.6") G1=69 mm (2.72") 18,5 mm (0.73") VEGASWING 61 6 Fig.
9 Supplement 34 mm (1.34") 178 mm (7.01") VEGASWING 61, options 1 2 Fig.
9 Supplement 9.3 Industrial property rights VEGA product lines are global protected by industrial property rights. Further information see www.vega.com. Only in U.S.A.: Further information see patent label at the sensor housing. VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte. Nähere Informationen unter www.vega.com. Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site www.
29225-EN-130409 Notes VEGASWING 61 • - transistor (NPN/PNP) 35
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information available at the time of printing. Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2013 VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info.de@vega.com www.vega.