Technical information

Technical Information
TI365O/98/en/01.10
185414 01/10 03
Ultrasonic Level Sensor
LUC-M**
Compact transmitters for non-contact
level measurement of fluids, pastes and
coarse bulk materials
Application
Continuous, non-contact level
measurement in fluids, pastes,
sullages and coarse bulk materials
Flow measurement in open channels
and measuring weirs
System integration via:
- HART (standard), 4 mA ... 20mA
- PROFIBUS PA
Maximum measuring range:
LUC-M10:
- 5 m (16.4 ft) in fluids
- 2 m (6.6 ft) in bulk materials
LUC-M20:
- 8 m (26.2 ft) in fluids
- 3,5 m (11.5 ft) in bulk materials
LUC-M30:
- 15 m (49.2 ft) in fluids
- 7 m (23 ft) in bulk materials
LUC-M40:
- 10 m (32.8 ft) in fluids
- 5 m (16.4 ft) in bulk materials
Features
Quick and simple commissioning via
menu-guided on-site operation with
four-line plain text display
Envelope curves on the on-site display
for simple diagnosis
Suitable for explosion hazardous
areas (Gas-Ex, Dust-Ex)
Linearisation function (up to 32 points)
for conversion of the measured value
into any unit of length, volume or flow
rate
Non-contact measurement method
minimizes service requirements
Optional remote display and operation
(up to 20 m from transmitter)
Installation possible from thread G1½
or 1½ NPT upwards
Integrated temperature sensor for
automatic correction of the
temperature dependent sound
velocity
LUC-M10
LUC-M40
LUC-M30
LUC-M20