ADDENDUM 1 This Addendum is issued by DIALOG® prior to Bid Closing Date to provide revisions, clarification or supplemental terms or conditions. All such revisions, clarifications or supplemental terms or conditions forms part of the Bid and Contract Documents, and amends the original Bid Documents titled: Project: Project No.: Dated: RDNO Athletic Park Amenities Building Project No.:04228V0100 2014-06-02 IFB The effects of this Addendum shall be included in the Bid Price.
RDNO Athletic Park Amenities Building Project No.:04228V0100 2014-07-29 1 00 91 13 Addendum No. 1 Page 1 General Bidders are reminded that with respect to the Bid Form, should any items be omitted or be illegible, should any alteration be made to the text, or should any condition be added on or submitted with the Bid Form that was not requested by the Consultant, their Bid may be declared invalid and rejected by the Owner.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 Mechanical Specification Prepared for: Dialog BC Architecture Engineering 406-611 Alexander Street Vancouver, BC Prepared by: Williams Engineering Canada Inc. Suite 304, 1912 Enterprise Way | Kelowna, BC | V1Y 9S9 Phone: 778.484.3900 Fax: 778.484.3901 Project #: 029042.00 RDNO ATHLETIC PARK AMENITIES BUILDINGS Michael Raiva P.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 Table of Contents 1 GENERAL ............................................................................................................................................. 4 2 DESCRIPTION OF WORK ................................................................................................................... 4 3 STANDARD OF ACCEPTANCE ................................................................................................
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 35 NATURAL GAS SYSTEM - PIPING, VALVES AND FITTINGS - ................................................... 21 36 ROOF DRAINS AND FLOOR DRAINS .......................................................................................... 22 37 PLUMBING FIXTURES AND TRIM ................................................................................................ 23 38 DOMESTIC WATER HEATER (DWH-1/2) ................................
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 1 GENERAL 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 2 It is the intention of these specifications and drawings to provide for a complete and fully operating mechanical system as described herein, and in complete accord with applicable codes and ordinances.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .2 .3 .4 .5 3 STANDARD OF ACCEPTANCE 3.1 3.2 3.3 3.4 3.5 4 4.2 Material/products considered to satisfy the specification, but of a manufacturer other than those named in the Specification may be submitted to the Consultant for consideration not later than five (5) working days prior to closing of tender Addition of manufacturer's names to the specifications will be in writing by the Consultant. EXISTING SERVICES 5.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 6.2 7 MISCELLANEOUS METAL 7.1 7.2 8 9.2 9.3 10.2 11.2 Lubricate all equipment prior to being operated, except sealed bearings, which shall be checked. Use the lubricant recommended by the manufacturer for the service for which the equipment is specified. ESCUTCHEONS 12.1 12.2 13 Provide removable protective guards on all exposed V-belt drives and shaft couplings in accordance with Worker's Compensation Board requirements.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 13.2 13.3 14 PENETRATION OF FIRE SEPARATIONS 14.1 15 Seal all pipe and duct penetrations through fire separations with "3M Fire Barrier" system or equal U.L. Listed system. TEMPORARY USE OF MECHANICAL SYSTEMS 15.1 15.2 15.3 15.4 16 Paint all pipe hangers and exposed sleeves, in exposed areas, with a rust inhibiting primer, as they are installed.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 .2 .3 .4 .5 .6 16.5 16.6 16.7 Balancing of the air systems as specified. Balancing of the liquid systems as specified. Balancing of domestic hot water recirculation systems. Set up air diffusers, registers and grilles for optimum distribution/comfort. Plug all air pressure and flow measuring holes. Adjust vibration isolators and seismic restraints for optimum performance. Provide letter of certification. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 17 SUBSTANTIAL PERFORMANCE REQUIREMENTS 17.1 17.2 18 .4 Pumps, fans, heaters, unit heaters and coils. .5 Sprinkler fire protection systems. .6 Sewage and septic installations. .7 Tanks - domestic hot water and expansion. After demonstration obtain the Owner's signature certifying that the demonstration has been performed and completed to their satisfaction.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 19 SYSTEMS BALANCING 19.1 19.2 19.3 19.4 19.5 19.6 19.7 20 The Contractor shall provide 6 copies of shop drawings of all equipment for the Consultant’s review. Submit clear and descriptive control sequences prior to installation. AS-INSTALLED RECORD DRAWINGS 21.1 21.2 21.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .5 22.2 22.3 23 SPARE PARTS 23.1 24 Provide spare parts for the Owner as follows: .1 one set of v-belts for each new piece of equipment. .2 one set of filter media for each filter or filter bank installed. .3 One box (12 cartridges) for each water filter installed. VIBRATION ISOLATION 24.1 24.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 25.5 25.6 25.7 25.8 25.9 25.10 26 Air terminals installed in grid ceilings on flexible duct shall have at least two galvanized steel seismic restraint wires attached to the building structure or to ceiling hanger wires. Attach security bridles at opposite corners of each air terminal and in such a manner that the air terminal cannot fall.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 .5 .6 .7 .8 26.9 26.10 26.11 26.12 26.13 Felt or neoprene anti-chatter blade strips. Blade connecting linkage with eyelet and pin bearings. Maximum blade length of 760 mm [30"], use multiples for larger dimensions. Manufacturer's label. Where a balanced backdraft damper (BBD) is indicated the damper shall incorporate an adjustable counterbalance weight and lever. .9 Maximum pressure drop across damper at 4.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 .5 At or to one side of other equipment in duct, (eg. Backdraft dampers, balancing dampers serving multiple inlets/outlets, Panels need not be provided where access is available through a door or a register mounted on the side of the duct. .2 26.14 26.15 26.16 27 Products: .1 Doors - construct in accordance with SMACNA Duct Standards Fig. 6-12 except for latch type. 40mm [1-1/2"] thick insulation. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 27.8 27.9 27.10 27.11 27.12 27.13 27.14 27.15 28 THERMOMETERS AND GAUGES 28.1 28.2 28.3 29 Arrange piping connections to allow ease of access and for removal of equipment. Align and independently support piping connections adjacent to equipment to prevent piping stresses being transferred. Install valves with stems upright or horizontal unless approved otherwise.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 29.5 30 All insulation accessories (adhesives, tape, coatings, etc.) shall be approved for the specific application. Duct Insulation Schedule: .1 Provide 25mm [1"] thermal insulation for outside air ducts. .2 Provide 25mm [1"] thermal insulation for exhaust ducts for 2.5m [8'] from roof or wall penetration. .3 Provide 25mm [1"] thermal insulation for all interior supply ducts. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 .5 .6 .7 .8 31 INSULATION - EQUIPMENT 31.1 31.2 31.3 31.4 31.5 32 Provide 25mm [1"] insulation for all heating pipes 50mm [2"] and smaller. 40mm [1.5"] for all heating pipes greater than 50mm [2"]. Provide 40mm [1.5"] insulation for all steam and condensate pipes 50mm [2"] and smaller, 50mm [2"] for all steam and condensate greater than 50mm [2"].
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 32.4 32.5 32.6 32.7 32.8 32.9 Acceptable Products: .1 Solder joint type: Red & White / Toyo 5049A, Apollo, Crane, Jenkins, Kitz, Lunkenheimer 746FS or 747FS, Neuman-Hattersley, Nibco, Watts, Worcester. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 .2 .3 33 DRAIN, WASTE AND VENT SYSTEMS - PIPING AND FITTINGS 33.1 33.2 33.3 34 A high flow or main pressure reducing valve; which shall be one pipe size smaller than the incoming or outflowing building service, and shall be provided with a strainer, a reducer and a shut off valve on the inlet side and a reducer and a shut off valve on the outlet side. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 34.6 34.7 34.8 34.9 34.10 34.11 34.12 34.13 34.14 34.15 .4 Long radius type for elbows and return bends. Joints .1 Brazing materials shall be SIL-FOS-15 phosphor-copper-silver alloy for copper piping jointed by copper fittings and silver solder for brass fittings. .2 Flexible connections: 3/8” nominal or less shall be made using coiled soft copper tubing.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 34.16 34.17 34.18 35 .2 Design pressure 2070 kPa [300 psig]. .3 Acceptable Products: Anaconda Install the following accessories: .1 Ball check isolating valves at receiver sight glass. .2 Charging valve for high and low side filter drier, solenoid valve and thermostatic expansion valve. Refrigerant Tests .1 Each refrigerant system shall be tested as follows before operation with dry nitrogen gas to a pressure not less than 1.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 .4 35.6 35.7 35.8 35.9 36 Suitable for the temperature to which exposed. Registered and bearing Province of British Columbia, Gas Inspection Department approval. .5 Acceptable Manufacturers: Emco, Homestead, Mueller, Newman Milliken, Wallaceburg Roof Supports .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37 PLUMBING FIXTURES AND TRIM 37.1 37.2 Acceptable Manufacturers .1 Acceptable manufacturers of plumbing fixtures: American Standard, Crane, Kohler, Toto. .2 Acceptable manufacturers of plumbing faucets and trim (except hands-free): Symmons, Cambridge Brass, Teck, Chicago, Crane, Zurn. .3 Acceptable manufacturers of hands-free plumbing faucets and flush valves: Sloan. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.3 37.4 Water Closet ‘WC-1’: .1 American Standard Afwall Millennium Flowise Elongated #3351.101.020 HET Toilet, white vitreous china with EverClean antimicrobial surface which inhibits the growth of stain and odor causing bacteria mold and mildew, Wall Hung, siphon jet flush action, operates in the range of 4.2 L to 6 L (1.1 US Gal to 1.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.5 37.6 Urinal ‘UR-1’: .1 American Standard Decorum Flowise #6042.005.020 Urinal, white vitreous china with EverClean antimicrobial surface which inhibits the growth of stain and odor causing bacteria mold and mildew, 1.9 L (0.5 US Gal) per flush, Wall Hung, washdown action, 19 mm (3/4") dia. Top spud, integral P-trap, outlet connection 51 mm (2"), wall hanger.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.7 37.8 37.9 Lavatory ‘LAV-2’: .1 American Standard Cadet #0236.004 Basin, 622 mm x 508 mm x (24-1/2" x 20" x 8") deep, vitreous china, for carrier with "U" bracket, rear overflow, faucet ledge, generous shelf area. Sloan Optima #ETF-600-LT Electronic Faucet, chrome plated, 4" (102mm) centerset, cast brass, 1.9 LPM (0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.10 37.11 37.12 37.13 Sink ‘SK-1’: .1 Franke Commercial #LBD6808-1/1 Double Bowl Countertop Mount Sink, 1 hole, 522 mm (20-9/16") x 995 mm (39-3/16") x 203 mm (8") deep, counter mounted, backledge, 18-10 type 302 20 GA. (0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.14 37.15 38 DOMESTIC WATER HEATER (DWH-1/2) 38.1 39 Natural gas water heater(s) shall be A. O. Smith Cyclone HE model # BTX-80, with 90% thermal efficiency, a storage capacity of 50 gallons, an input rating of 76,000 BTUs per hour, a recovery rating of 83 gallons per hour at 100ºF rise and a maximum hydrostatic working pressure of 150 psi.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 40.2 40.3 40.4 40.5 40.6 40.7 40.8 40.9 40.10 41 Control system shall be an electronic system. The system architecture shall utilize intelligent distributed control modules, located at each piece of equipment, which will communicate on a peer to peer LAN trunk.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 .2 .3 .4 .3 41.2 .1 .2 Control Damper CD-1 shall open. MUA-1 shall start Exhaust Fans EF-1 and EF-2 shall start The system shall operate until space temperatures are achieved (as sensed by the averaging temperature sensors) and for a minimum of 15 minutes. .2 Occupied Mode: .1 MUA-1 shall operate in occupied/unoccupied mode according to a user defined schedule. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 41.3 .1 .2 .1 MUA-2 shall operate in occupied/unoccupied mode according to a user defined schedule. .2 When MUA-2 is operating in occupied mode the outdoor air dampers, fans and the refrigeration compressors shall operate in sequence to maintain the supply air temperature at setpoint. .3 The space temperature setpoint shall be 14°C (58°F) in winter and 24°C (75°F) in summer. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 42 Fail safe Mode: .1 In the event of a power failure, all systems shall revert to off position and restart when power is restored if required. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES MAKE-UP AIR UNITS - ROOFTOP MS125 UNIT NO MUA-1 MUA-2 SERVICE Washroom Change Room HEATING: CAPACITY (kW) (BTUh) EDB. (C) (F) TYPE: 82.07 280000.00 -20.00 -4.00 Indirect Fired 164.14 560000.00 -20.00 -4.00 Indirect Fired SUPPLY FAN: AIR FLOW (L/s) (CFM) S.P. (Pa) (ins) FAN DRAW (BHP) 1415.70 3000.00 186.83 0.75 2.00 2831.40 6000.00 186.83 0.75 5.00 GAS FURNACE: INPUT (kW) (MBH) 102.59 350.00 0.21 700.00 FAN MOTOR (HP) 3.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 NOTATION MECHANICAL SCHEDULES AIR TERMINALS MS140 SECTION 23 06 00 A B C MANUFACTURER E.H.PRICE E.H.PRICE E.H.PRICE TYPE Heavy Duty Heavy Duty Round Plaque 96 90 RPD BORDER - - - BLADE ORIENT. L L CORE STYLE - - - VANES - - - NO OF SLOTS - - - Refer to dwgs Refer to dwgs 250mm VOLUME DAMPER D D - MOUNTING FRAME - - - FASTENING A A - As per Arch. As per Arch. As per Arch. 1 1 2 MODEL NO NOM.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES CONDENSING UNITS - AIR COOLED MS240 UNIT NO CU -1 CU -2 CU -3 SERVICE MUA-1 MUA-2 FC-1 OUTSIDE OUTSIDE OUTSIDE CAPACITY (kW) (BTUh) 24.74 84400 51.85 176900 10.49 35800 REFRIGERANT R-410a R-410a R-410a 1416 3000 2831 6000 AMBIENT AIR: MAX TEMP.
RDNO ATHLETIC AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES CONTROL DAMPERS MS260 SECTION 23 06 00 UNIT NO CD - 1 CD - 2 CD - 3 CD - 4 SERVICE MUA-1 FCU-1 FCU-1 MUA-2 AIR STREAM O/A O/A R/A O/A FLOW (L/s) (CFM) 1416 3000 118 250 448 950 2831 6000 1050X950 500x500 600x450 1200x1200 CLOSED CLOSED OPEN CLOSED 2P 2P 2P 2P SIZE: W X H (mm) VELOCITY (m/s) (F/M) NORMAL POSITION TYPE DAMPER TYPE: 2P - 2 POSITION MOD - MODULATING NORMAL POSITION IS "BENCH" POSITION MS260
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES FANS - EXHAUST MS310 SECTION 23 06 00 UNIT NO EF-1 EF-2 EF-3 EF-4 SERVICE Washroom - Lower Washroom - Upper Change Room Classroom LOCATION Washroom - Lower Female WC 206 Mech Room 311 Classroom 309 590 1,250 543 1,150 2,831 6,000 118 250 125 0.5 125 0.5 125 0.5 125 0.5 1725 1382 734 1245 DIRECT BELT DIRECT DIRECT FAN MOTOR (HP) 0.25 0.5 1.5 0.
RDNO ATHLETIC AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES FAN COIL UNITS - DX MS341 UNIT NO FCU -1 SERVICE Classroom LOCATION HEATING: TOTAL (kW) (BTUh) COOLING: TOTAL (kW) (BTUh) SENS. (kW) (BTUh) EDB. (C) (F) EWB. (C) (F) LDB. (C) (F) LWB. (C) (F) COIL REFRIG. (C) (F) Classroom 309 8.29 28278 13.14 44830 9.15 31220 26.7 80.0 19.4 67.0 13.5 56.3 12.8 55.0 7.2 45.0 REFRIGERANT R-410A SUPPLY FAN: FLOW (L/s) (CFM) EXT.S.P.(Pa) (ins) FAN RPM 566 1200 125 0.50 FAN MOTOR (HP) 0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES LOUVRES MS470 SECTION 23 06 00 UNIT NO LV-1 LV-2 LV-3 LV-4 LV-5 SERVICE MUA-1 MUA-2 EF-1 EF-2 EF-3 Washroom Mechanical Room ChangeRoom Mechanical Room Storage Room Female Washroom ChangeRoom Mechanical Room LOUVRE SIZE: WIDTH (mm) (ins) HEIGHT (mm) (ins) DEPTH (mm) (ins) 1067 42 660 26 102 4 1219 48 1270 50 102 4 457 18 356 14 102 4 610 24 457 18 102 4 610 24 CAPACITY (L/s) (CFM) 1416 3000 3539 7500 1416 3000
UNIT NO LV-6 LV-7 LV-8 SERVICE MUA-1 MUA-2 FCU-1 Washroom Mechanical Room ChangeRoom Mechanical Room Classroom 254 10 254 10 102 4 406 16 406 16 102 4 610 24 457 18 102 4 LOCATION LOUVRE SIZE: WIDTH (mm) (ins) HEIGHT (mm) (ins) DEPTH (mm) (ins) CAPACITY (L/s) (CFM) 118 250 FACE VEL.(m/s) (F/M) 4.32 850 AIR P.D. (Pa) (ins) 25 0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES PUMPS MS500 UNIT NO P -1 P -2 SERVICE DWH-1 DHW-2 Washroom Mech Change Room Mech DWH Recirc DWH Recirc CAPACITY (L/s) (USGPM) 0.32 5 0.32 5 LIQUID water water LIQUID TEMP.(C) (F) 60.0 140.0 60.0 140.0 DIFF.PRESS.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES TANKS MS540 UNIT NO ET-1 ET-2 SERVICE DWH-1 DWH-2 Washroom Mech. Room Washroom Mech. Room 1034 150 1034 150 CAPACITY (L) (USGAL) 24 6 24 6 TANK DIMENSIONS: DIAMETER (mm) (ins) LENGTH (mm) (ins) 305 12 330 13 305 12 330 13 Inline Vertical Inline Vertical Amtrol Amtrol ST-12-C ST-12-C 1 1 LOCATION WK.PRESS. (kPa) (PSI) ARRANGEMENT MANUFACTURER MODEL NO SEE NOTE(S) 1.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 Mechanical Specification Alternate Price Prepared for: Dialog BC Architecture Engineering 406-611 Alexander Street Vancouver, BC Prepared by: Williams Engineering Canada Inc. Suite 304, 1912 Enterprise Way | Kelowna, BC | V1Y 9S9 Phone: 778.484.3900 Fax: 778.484.3901 Project #: 029042.00 RDNO ATHLETIC PARK AMENITIES BUILDINGS Michael Raiva P.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 Table of Contents 1 GENERAL ............................................................................................................................................. 4 2 DESCRIPTION OF WORK ................................................................................................................... 4 3 STANDARD OF ACCEPTANCE ................................................................................................
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 35 NATURAL GAS SYSTEM - PIPING, VALVES AND FITTINGS - ................................................... 21 36 ROOF DRAINS AND FLOOR DRAINS .......................................................................................... 22 37 PLUMBING FIXTURES AND TRIM ................................................................................................ 23 38 DOMESTIC WATER HEATER (DWH-1/2) ................................
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 1 GENERAL 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 2 It is the intention of these specifications and drawings to provide for a complete and fully operating mechanical system as described herein, and in complete accord with applicable codes and ordinances.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .2 .3 .4 .5 3 STANDARD OF ACCEPTANCE 3.1 3.2 3.3 3.4 3.5 4 4.2 Material/products considered to satisfy the specification, but of a manufacturer other than those named in the Specification may be submitted to the Consultant for consideration not later than five (5) working days prior to closing of tender Addition of manufacturer's names to the specifications will be in writing by the Consultant. EXISTING SERVICES 5.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 6.2 7 MISCELLANEOUS METAL 7.1 7.2 8 9.2 9.3 10.2 11.2 Lubricate all equipment prior to being operated, except sealed bearings, which shall be checked. Use the lubricant recommended by the manufacturer for the service for which the equipment is specified. ESCUTCHEONS 12.1 12.2 13 Provide removable protective guards on all exposed V-belt drives and shaft couplings in accordance with Worker's Compensation Board requirements.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 13.2 13.3 14 PENETRATION OF FIRE SEPARATIONS 14.1 15 Seal all pipe and duct penetrations through fire separations with "3M Fire Barrier" system or equal U.L. Listed system. TEMPORARY USE OF MECHANICAL SYSTEMS 15.1 15.2 15.3 15.4 16 Paint all pipe hangers and exposed sleeves, in exposed areas, with a rust inhibiting primer, as they are installed.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 .2 .3 .4 .5 .6 16.5 16.6 16.7 Balancing of the air systems as specified. Balancing of the liquid systems as specified. Balancing of domestic hot water recirculation systems. Set up air diffusers, registers and grilles for optimum distribution/comfort. Plug all air pressure and flow measuring holes. Adjust vibration isolators and seismic restraints for optimum performance. Provide letter of certification. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 17 SUBSTANTIAL PERFORMANCE REQUIREMENTS 17.1 17.2 18 .4 Pumps, fans, heaters, unit heaters and coils. .5 Sprinkler fire protection systems. .6 Sewage and septic installations. .7 Tanks - domestic hot water and expansion. After demonstration obtain the Owner's signature certifying that the demonstration has been performed and completed to their satisfaction.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 19 SYSTEMS BALANCING 19.1 19.2 19.3 19.4 19.5 19.6 19.7 20 The Contractor shall provide 6 copies of shop drawings of all equipment for the Consultant’s review. Submit clear and descriptive control sequences prior to installation. AS-INSTALLED RECORD DRAWINGS 21.1 21.2 21.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .5 22.2 22.3 23 SPARE PARTS 23.1 24 Provide spare parts for the Owner as follows: .1 one set of v-belts for each new piece of equipment. .2 one set of filter media for each filter or filter bank installed. .3 One box (12 cartridges) for each water filter installed. VIBRATION ISOLATION 24.1 24.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 25.5 25.6 25.7 25.8 25.9 25.10 26 Air terminals installed in grid ceilings on flexible duct shall have at least two galvanized steel seismic restraint wires attached to the building structure or to ceiling hanger wires. Attach security bridles at opposite corners of each air terminal and in such a manner that the air terminal cannot fall.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 .5 .6 .7 .8 26.9 26.10 26.11 26.12 26.13 Felt or neoprene anti-chatter blade strips. Blade connecting linkage with eyelet and pin bearings. Maximum blade length of 760 mm [30"], use multiples for larger dimensions. Manufacturer's label. Where a balanced backdraft damper (BBD) is indicated the damper shall incorporate an adjustable counterbalance weight and lever. .9 Maximum pressure drop across damper at 4.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 .5 At or to one side of other equipment in duct, (eg. Backdraft dampers, balancing dampers serving multiple inlets/outlets, Panels need not be provided where access is available through a door or a register mounted on the side of the duct. .2 26.14 26.15 26.16 27 Products: .1 Doors - construct in accordance with SMACNA Duct Standards Fig. 6-12 except for latch type. 40mm [1-1/2"] thick insulation. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 27.8 27.9 27.10 27.11 27.12 27.13 27.14 27.15 28 THERMOMETERS AND GAUGES 28.1 28.2 28.3 29 Arrange piping connections to allow ease of access and for removal of equipment. Align and independently support piping connections adjacent to equipment to prevent piping stresses being transferred. Install valves with stems upright or horizontal unless approved otherwise.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 29.5 30 All insulation accessories (adhesives, tape, coatings, etc.) shall be approved for the specific application. Duct Insulation Schedule: .1 Provide 25mm [1"] thermal insulation for outside air ducts. .2 Provide 25mm [1"] thermal insulation for exhaust ducts for 2.5m [8'] from roof or wall penetration. .3 Provide 25mm [1"] thermal insulation for all interior supply ducts. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .4 .5 .6 .7 .8 31 INSULATION - EQUIPMENT 31.1 31.2 31.3 31.4 31.5 32 Provide 25mm [1"] insulation for all heating pipes 50mm [2"] and smaller. 40mm [1.5"] for all heating pipes greater than 50mm [2"]. Provide 40mm [1.5"] insulation for all steam and condensate pipes 50mm [2"] and smaller, 50mm [2"] for all steam and condensate greater than 50mm [2"].
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 32.4 32.5 32.6 32.7 32.8 32.9 Acceptable Products: .1 Solder joint type: Red & White / Toyo 5049A, Apollo, Crane, Jenkins, Kitz, Lunkenheimer 746FS or 747FS, Neuman-Hattersley, Nibco, Watts, Worcester. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 .2 .3 33 DRAIN, WASTE AND VENT SYSTEMS - PIPING AND FITTINGS 33.1 33.2 33.3 34 A high flow or main pressure reducing valve; which shall be one pipe size smaller than the incoming or outflowing building service, and shall be provided with a strainer, a reducer and a shut off valve on the inlet side and a reducer and a shut off valve on the outlet side. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 34.6 34.7 34.8 34.9 34.10 34.11 34.12 34.13 34.14 34.15 .4 Long radius type for elbows and return bends. Joints .1 Brazing materials shall be SIL-FOS-15 phosphor-copper-silver alloy for copper piping jointed by copper fittings and silver solder for brass fittings. .2 Flexible connections: 3/8” nominal or less shall be made using coiled soft copper tubing.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 34.16 34.17 34.18 35 .2 Design pressure 2070 kPa [300 psig]. .3 Acceptable Products: Anaconda Install the following accessories: .1 Ball check isolating valves at receiver sight glass. .2 Charging valve for high and low side filter drier, solenoid valve and thermostatic expansion valve. Refrigerant Tests .1 Each refrigerant system shall be tested as follows before operation with dry nitrogen gas to a pressure not less than 1.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 .4 35.6 35.7 35.8 35.9 36 Suitable for the temperature to which exposed. Registered and bearing Province of British Columbia, Gas Inspection Department approval. .5 Acceptable Manufacturers: Emco, Homestead, Mueller, Newman Milliken, Wallaceburg Roof Supports .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37 PLUMBING FIXTURES AND TRIM 37.1 37.2 Acceptable Manufacturers .1 Acceptable manufacturers of plumbing fixtures: American Standard, Crane, Kohler, Toto. .2 Acceptable manufacturers of plumbing faucets and trim (except hands-free): Symmons, Cambridge Brass, Teck, Chicago, Crane, Zurn. .3 Acceptable manufacturers of hands-free plumbing faucets and flush valves: Sloan. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.3 37.4 Water Closet ‘WC-1’: .1 American Standard Afwall Millennium Flowise Elongated #3351.101.020 HET Toilet, white vitreous china with EverClean antimicrobial surface which inhibits the growth of stain and odor causing bacteria mold and mildew, Wall Hung, siphon jet flush action, operates in the range of 4.2 L to 6 L (1.1 US Gal to 1.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.5 37.6 Urinal ‘UR-1’: .1 American Standard Decorum Flowise #6042.005.020 Urinal, white vitreous china with EverClean antimicrobial surface which inhibits the growth of stain and odor causing bacteria mold and mildew, 1.9 L (0.5 US Gal) per flush, Wall Hung, washdown action, 19 mm (3/4") dia. Top spud, integral P-trap, outlet connection 51 mm (2"), wall hanger.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.7 37.8 37.9 Lavatory ‘LAV-2’: .1 American Standard Cadet #0236.004 Basin, 622 mm x 508 mm x (24-1/2" x 20" x 8") deep, vitreous china, for carrier with "U" bracket, rear overflow, faucet ledge, generous shelf area. Sloan Optima #ETF-600-LT Electronic Faucet, chrome plated, 4" (102mm) centerset, cast brass, 1.9 LPM (0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.10 37.11 37.12 37.13 Sink ‘SK-1’: .1 Franke Commercial #LBD6808-1/1 Double Bowl Countertop Mount Sink, 1 hole, 522 mm (20-9/16") x 995 mm (39-3/16") x 203 mm (8") deep, counter mounted, backledge, 18-10 type 302 20 GA. (0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 37.14 37.15 38 DOMESTIC WATER HEATER (DWH-1/2) 38.1 39 Natural gas water heater(s) shall be A. O. Smith Cyclone HE model # BTX-80, with 90% thermal efficiency, a storage capacity of 50 gallons, an input rating of 76,000 BTUs per hour, a recovery rating of 83 gallons per hour at 100ºF rise and a maximum hydrostatic working pressure of 150 psi.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 40.2 40.3 40.4 40.5 40.6 40.7 40.8 40.9 40.10 41 Control system shall be an electronic system. The system architecture shall utilize intelligent distributed control modules, located at each piece of equipment, which will communicate on a peer to peer LAN trunk.
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .1 .2 .3 .4 .3 41.2 .1 .2 Control Damper CD-1 shall open. MUA-1 shall start Exhaust Fans EF-1 and EF-2 shall start The system shall operate until space temperatures are achieved (as sensed by the averaging temperature sensors) and for a minimum of 15 minutes. .2 Occupied Mode: .1 MUA-1 shall operate in occupied/unoccupied mode according to a user defined schedule. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 41.3 .1 .2 .1 MUA-2 shall operate in occupied/unoccupied mode according to a user defined schedule. .2 When MUA-2 is operating in occupied mode the outdoor air dampers, fans and the refrigeration compressors shall operate in sequence to maintain the supply air temperature at setpoint. .3 The space temperature setpoint shall be 14°C (58°F) in winter and 24°C (75°F) in summer. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS WE File No.029042.00 May 30, 2014 .3 42 Fail safe Mode: .1 In the event of a power failure, all systems shall revert to off position and restart when power is restored if required. .
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES MAKE-UP AIR UNITS - ROOFTOP MS125 UNIT NO MUA-1 MUA-2 SERVICE Washroom Change Room HEATING: CAPACITY (kW) (BTUh) EDB. (C) (F) TYPE: 82.07 280000.00 -20.00 -4.00 Indirect Fired 164.14 560000.00 -20.00 -4.00 Indirect Fired SUPPLY FAN: AIR FLOW (L/s) (CFM) S.P. (Pa) (ins) FAN DRAW (BHP) 1415.70 3000.00 186.83 0.75 2.00 2831.40 6000.00 186.83 0.75 5.00 GAS FURNACE: INPUT (kW) (MBH) 102.59 350.00 0.21 700.00 FAN MOTOR (HP) 3.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 NOTATION MECHANICAL SCHEDULES AIR TERMINALS MS140 SECTION 23 06 00 A B C MANUFACTURER E.H.PRICE E.H.PRICE E.H.PRICE TYPE Heavy Duty Heavy Duty Round Plaque 96 90 RPD BORDER - - - BLADE ORIENT. L L CORE STYLE - - - VANES - - - NO OF SLOTS - - - Refer to dwgs Refer to dwgs 250mm VOLUME DAMPER D D - MOUNTING FRAME - - - FASTENING A A - As per Arch. As per Arch. As per Arch. 1 1 2 MODEL NO NOM.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES CONDENSING UNITS - AIR COOLED MS240 UNIT NO CU -1 CU -2 CU -3 SERVICE MUA-1 MUA-2 FC-1 OUTSIDE OUTSIDE OUTSIDE CAPACITY (kW) (BTUh) 24.74 84400 51.85 176900 10.49 35800 REFRIGERANT R-410a R-410a R-410a 1416 3000 2831 6000 AMBIENT AIR: MAX TEMP.
RDNO ATHLETIC AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES CONTROL DAMPERS MS260 SECTION 23 06 00 UNIT NO CD - 1 CD - 2 CD - 3 CD - 4 SERVICE MUA-1 FCU-1 FCU-1 MUA-2 AIR STREAM O/A O/A R/A O/A FLOW (L/s) (CFM) 1416 3000 118 250 448 950 2831 6000 1050X950 500x500 600x450 1200x1200 CLOSED CLOSED OPEN CLOSED 2P 2P 2P 2P SIZE: W X H (mm) VELOCITY (m/s) (F/M) NORMAL POSITION TYPE DAMPER TYPE: 2P - 2 POSITION MOD - MODULATING NORMAL POSITION IS "BENCH" POSITION MS260
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES FANS - EXHAUST MS310 SECTION 23 06 00 UNIT NO EF-1 EF-2 EF-3 EF-4 SERVICE Washroom - Lower Washroom - Upper Change Room Classroom LOCATION Washroom - Lower Female WC 206 Mech Room 311 Classroom 309 590 1,250 543 1,150 2,831 6,000 118 250 125 0.5 125 0.5 125 0.5 125 0.5 1725 1382 734 1245 DIRECT BELT DIRECT DIRECT FAN MOTOR (HP) 0.25 0.5 1.5 0.
RDNO ATHLETIC AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES FAN COIL UNITS - DX MS341 UNIT NO FCU -1 SERVICE Classroom LOCATION HEATING: TOTAL (kW) (BTUh) COOLING: TOTAL (kW) (BTUh) SENS. (kW) (BTUh) EDB. (C) (F) EWB. (C) (F) LDB. (C) (F) LWB. (C) (F) COIL REFRIG. (C) (F) Classroom 309 8.29 28278 13.14 44830 9.15 31220 26.7 80.0 19.4 67.0 13.5 56.3 12.8 55.0 7.2 45.0 REFRIGERANT R-410A SUPPLY FAN: FLOW (L/s) (CFM) EXT.S.P.(Pa) (ins) FAN RPM 566 1200 125 0.50 FAN MOTOR (HP) 0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES LOUVRES MS470 SECTION 23 06 00 UNIT NO LV-1 LV-2 LV-3 LV-4 LV-5 SERVICE MUA-1 MUA-2 EF-1 EF-2 EF-3 Washroom Mechanical Room ChangeRoom Mechanical Room Storage Room Female Washroom ChangeRoom Mechanical Room LOUVRE SIZE: WIDTH (mm) (ins) HEIGHT (mm) (ins) DEPTH (mm) (ins) 1067 42 660 26 102 4 1219 48 1270 50 102 4 457 18 356 14 102 4 610 24 457 18 102 4 610 24 CAPACITY (L/s) (CFM) 1416 3000 3539 7500 1416 3000
UNIT NO LV-6 LV-7 LV-8 SERVICE MUA-1 MUA-2 FCU-1 Washroom Mechanical Room ChangeRoom Mechanical Room Classroom 254 10 254 10 102 4 406 16 406 16 102 4 610 24 457 18 102 4 LOCATION LOUVRE SIZE: WIDTH (mm) (ins) HEIGHT (mm) (ins) DEPTH (mm) (ins) CAPACITY (L/s) (CFM) 118 250 FACE VEL.(m/s) (F/M) 4.32 850 AIR P.D. (Pa) (ins) 25 0.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES PUMPS MS500 UNIT NO P -1 P -2 SERVICE DWH-1 DHW-2 Washroom Mech Change Room Mech DWH Recirc DWH Recirc CAPACITY (L/s) (USGPM) 0.32 5 0.32 5 LIQUID water water LIQUID TEMP.(C) (F) 60.0 140.0 60.0 140.0 DIFF.PRESS.
RDNO ATHLETIC PARK AMENITIES BUILDINGS May 2014 MECHANICAL SCHEDULES TANKS MS540 UNIT NO ET-1 ET-2 SERVICE DWH-1 DWH-2 Washroom Mech. Room Washroom Mech. Room 1034 150 1034 150 CAPACITY (L) (USGAL) 24 6 24 6 TANK DIMENSIONS: DIAMETER (mm) (ins) LENGTH (mm) (ins) 305 12 330 13 305 12 330 13 Inline Vertical Inline Vertical Amtrol Amtrol ST-12-C ST-12-C 1 1 LOCATION WK.PRESS. (kPa) (PSI) ARRANGEMENT MANUFACTURER MODEL NO SEE NOTE(S) 1.