Specifications

RDNO ATHLETIC PARK
AMENITIES BUILDINGS
WE File No.029042.00
May 30, 2014
11 | P a g e
.5 Identification colour bands for primary and secondary colours to indicate the type
and degree of hazard shall be applied to overlap a minimum of 50mm [2"]. Bands
shall be Brady B550 vinyl cloth tape or Brady B946 vinyl tape, with adhesive
compatible with the surface temperature.
22.2 Each piece of equipment shall be identified with its equipment schedule identification, e.g.
supply fan SF-1, cooling coil CC-1, pump P-1.
.1 Provide laminated plastic plates with black face and white centre of minimum size
90mm x 40mm x 2.5mm [3-1/2" x 1-1/2" x 3/32"] engraved with 12mm [1/2"] high
lettering. Use 25mm [1"] high lettering for major equipment.
.2 Apply nameplates securely in conspicuous places, on cool surfaces.
22.3 Secure 6mm [1/4"] self adhesive coloured dots, (Brady Quik Dots or Avery Data Dots), to
the ceiling, to identify the location of access to equipment concealed above the ceiling
23 SPARE PARTS
23.1 Provide spare parts for the Owner as follows:
.1 one set of v-belts for each new piece of equipment.
.2 one set of filter media for each filter or filter bank installed.
.3 One box (12 cartridges) for each water filter installed.
24 VIBRATION ISOLATION
24.1 Provide vibration isolation on all motor driven equipment with motors of ½ HP and greater
power output (as indicated on the motor nameplate) and on piping and ductwork, as
specified herein. For equipment less than ½ HP, provide neoprene grommets at the
support points.
24.2 Provide 20mm [3/4"] thick continuous perimeter closed cell foam gasket to isolate base of
package type equipment, AHU's, exhaust fans, etc. from floors, roofs and roof curbs.
Select width for nominal 3 psig loading under weight of equipment and allow for 25%
compression, 5mm [3/16"]. Increase width of curb using steel shim if necessary to
accommodate gasket. For light equipment such as exhaust fans, deflection should be a
minimum of 0.05". Use hold down bolts selected for seismic loads. Isolate bolts from base
of unit using neoprene hemi-grommets. Avoid compressing gasket (eg. use Hilti HVA
adhesive set bolts, or equal, with steel washers and lock nuts, adjusted finger tight to the
hemi-grommets). Size bolt and hemi-grommet for minimum lateral clearance. Standard of
Acceptance: American National Rubber-EPDM-SBR blend SCE 41 type self-extinguishing
neoprene, Mason Industries Type HG Hemi-Grommets
25 SEISMIC RESTRAINTS
25.1 Provide cable restraints on all isolated equipment and seismic restraint on all other
equipment, piping and ductwork, all in general accordance with SMACNA Guidelines
25.2 Include in the Tender the services of a BC Professional engineer, regularly employed in the
design of restraint systems to review and sign-off on all seismic supports and restraints.
Submit "sealed and signed" Letters of Assurance from the Seismic Engineer.
25.3 It is the entire responsibility of equipment manufacturers to design their equipment so that
the strength and anchorage of internal components of the equipment exceeds the force
level used to restrain and anchor the unit itself to the supporting structure.
25.4 All resiliently mounted equipment, including piping and ductwork, shall be provided with
seismic restraining devices (snubbers).