Specifications

RDNO ATHLETIC PARK MECHANICAL SCHEDULES SECTION 23 06 00
AMENITIES BUILDINGS FANS - EXHAUST
May 2014 MS310
UNIT NO EF-1 EF-2 EF-3 EF-4
SERVICE Washroom - Lower Washroom - Upper Change Room Classroom
LOCATION Washroom - Lower Female WC 206 Mech Room 311 Classroom 309
FAN TYPE
AIR FLOW (L/s) 590 543 2,831 118
(CFM) 1,250 1,150 6,000 250
FAN S.P. (Pa) 125 125 125 125
(ins) 0.5 0.5 0.5 0.5
FAN DRAW
FAN (RPM) 1725 1382 734 1245
DRIVE TYPE DIRECT BELT DIRECT DIRECT
FAN MOTOR (HP) 0.25 0.5 1.5 0.5
VOLTS/Hz/PHASE 115/60/1 115/60/1 115/60/1 115/60/1
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NO BDF-80-5 SQ-100-A BSQ-240-15 SQ-80-4
SEE NOTE(S) 1 1 1 1
NOTES:
1 - Provide backdraft damper at outlet of fan.
MS310 FAN EXH