Product Data Manual HRV600i • HRV700i • HRV1200i • HRV2000i/e HRV2000e
Table of Contents Physical Data - Nomenclature Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Effectiveness Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Airflow Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Data - Nomenclature Options UNIT NOMENCLATURE OPTIONS FROST CONTROL Recirculation Exhaust only Non defrost Non defrost, no wall control compatibility Preheat frost prevention VOLTAGE/SPEED 208-230 VAC/1/60 - 1 Speed 208-230 VAC/3/60 - 1 Speed 460 VAC/3/60 - 1 Speed 575 VAC/3/60 - 1 Speed 120 VAC/1/60 - 2 Speed 208-230 VAC/1/60 - 2 Speed ENERGY RECOVERY Polypropylene core Aluminum core HM core INTERNAL PROTECTION 1" insulation, single wall (R4) 1" insulation, double wall (R4) Corrosion resistant R4,
Physical Data - Nomenclature Options UNIT NOMENCLATURE OPTIONS HOODS Intake/exhaust hoods No hoods SUPPLY DISCHARGE End supply discharge Down supply discharge RETURN AIR End return air inlet Bottom return air inlet FILTERS Supply AL mesh pre-filter Supply MEF (30%) DSE Supply HEF (80 - 85%) DSE Exhaust MEF (30%) DSE Supply washable foam 20ppm Exhaust washable foam 20ppm ACCESS DOOR Standard door Reverse door LOW SPEED Reduced low speed Normal low speed Legend: B - Included in base unit O - Optional 600i
Physical Data FANS Model Name Supply Type Wheel Type Wheel Size (Inches) Wheel Size [mm] Bearing Housing Shaft [mm] Exhaust Type Wheel Type Wheel Size (Inches) Wheel Size [mm] Bearing Housing Shaft [mm] HRV600i HRV700i Type Size (Inches) Size [mm] Flat Plate Material Model Name Belt drive Forward curved 12Ø x 7 305Ø x 178 Ball sealed Resilient rings Cold rolled 1" [25] keyed Belt drive Forward curved 12Ø x 7 305Ø x 178 Ball sealed Resilient rings Cold rolled 1" [25] keyed Belt drive Forward curv
Effectiveness Performance Data HRV600i - POLYPROPYLENE AND ALUMINUM CORES Effectiveness 94 70% 165 Airflow (L/s) 236 307 378 Model Number: PHE500-13.1H-12S-0.11 Model Number: AHE500-13.1H-12S-0.14T Type: Plate (Plate) Nominal Airflow: 200 (200) scfm Pressure Drop: 0.22 (0.09) inches 50% Leakage Ratings Pressure Differential Test 1: -5.00 (-3.00) inches Test 2: 0.00 (0.00) inches Test 3: 5.00 (3.
Effectiveness Performance Data HRV700i - POLYPROPYLENE CORE Effectiveness 142 80% 201 Airflow (L/s) 260 319 378 Model Number: PHE500-19H-23S-0.12 Type: Plate Pressure Drop: 0.25 inches Nominal Airflow: 400 scfm Leakage Ratings 60% Test 1: Test 2: Test 3: 40% Pressure Differential -5.00 inches 0.00 inches 5.00 inches EATR 0% 0% 0% OACF 1.00 1.00 1.
Effectiveness Performance Data HRV1200i - POLYPROPYLENE AND ALUMINUM CORES Effectiveness 189 70% 307 Airflow (L/s) 472 590 661 Model Number: PHE500-13.1H-12S-0.11 Model Number: AHE500-13.1H-12S-0.14T Type: Plate (Plate) Nominal Airflow: 200 (200) scfm Pressure Drop: 0.22 (0.09) inches 50% Leakage Ratings Test 1: Test 2: Test 3: 30% 10% 400 650 1000 1250 Airflow (cfm) 1400 Based on equal amounts of outdoor air and return air.
Effectiveness Performance Data HRV2000i/e - POLYPROPYLENE AND ALUMINUM CORES Effectiveness 472 70% 684 Airflow (L/s) 897 1109 1322 Model Number: PHE500-15.4H-15.3S-0.11 Model Number: AHE500-15.4H-15S-0.14 Type: Plate (Plate) Nominal Airflow: 530 (530) scfm Pressure Drop: 0.86 (0.30) inches 50% Leakage Ratings Test 1: Test 2: Test 3: 30% 10% 1000 1450 1900 2350 Airflow (cfm) 2800 Based on equal amounts of outdoor air and return air.
Airflow Performance Data HRV600i AIRFLOW (CFM) ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 Low 650 635 611 595 570 544 517 488 447 322 256 Reduced Low 474 456 447 442 428 418 403 382 354 311 253 Medium 734 707 686 657 635 603 579 544 507 447 291 Reduced Medium 574 569 557 546 528 510 478 452 416 376 332 HRV700i AIRFLOW (CFM) High 791 764 735 705 682 650 625 589 542 491 322 NOTE: Medium tap can be installed by exchanging the low tap for medium (see wiring diagram).
Airflow Performance Data HRV2000i SUPPLY AND EXHAUST AIRFLOW PERFORMANCE HRV2000e SUPPLY AIRFLOW PERFORMANCE Airflow (cfm) 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 0.0 RPM BHP 597 0.19 637 0.24 676 0.28 713 0.34 748 0.40 785 0.47 818 0.55 853 0.63 892 0.73 925 0.83 960 0.94 995 1.03 1029 1.19 1062 1.32 1095 1.46 1129 1.62 1161 1.79 0.2 RPM BHP 695 0.24 729 0.29 762 0.34 794 0.41 826 0.47 858 0.55 889 0.62 923 0.72 957 0.81 989 0.92 1021 1.03 1054 1.16 1086 1.
Page 12 10.005" [254] LEFT VIEW SUPPLY AIR OPENING EXHAUST AIR OPENING 14.000" [356] CONTROL BOX ACCESS LOW VOLTAGE TERMINAL STRIPS SUPPLY AIR EXHAUST AIR LINE VOLTAGE IN 4.028" [102] A 5.859" [149] C 5.125" [130] D RETURN AIR OUTDOOR AIR FRONT VIEW NOTE: For units with the reversed door option, interior components will appear as a mirror image of the above diagram. 19.207" [488] 34.000" [864] TOP VIEW 13.375" [340] B B A B 7.705" [196] 14.
3.530" [90] 8.000" [203] 4.000" 24.500" [102] [622] 8.000" [203] 1.750" [44] 4.000" [102] LEFT VIEW EXHAUST AIR LINE VOLTAGE IN CONTROL BOX Page 13 5.125" 130] For Recirc Defrost Only FRONT VIEW 12.000" [305] FRONT VIEW ACCESS DOOR B A CONDENSATE DRAIN 7.100" [180] RIGHT VIEW 14.100" [358] RETURN AIR OPENING OUTDOOR AIR OPENING 14.000" [356] 1.750" [44] 8.000" [203] 4.000" [102] 8.000" [203] 15.000" [381] RIGHT VIEW REVERSED DOOR OPTION NOTE: A minimum of 15.
Page 14 LEFT VIEW SUPPLY AIR OPENING EXHAUST AIR OPENING 20.000" [508] 11.325" [288] A CONTROL BOX ACCESS SUPPLY AIR EXHAUST AIR LINE VOLTAGE IN LOW VOLTAGE TERMINAL STRIPS 4.028" [102] 5.715" [145] C 5.125" [130] D RETURN AIR OUTDOOR AIR FRONT VIEW B A B RETURN AIR OPENING 9.878" [251] RIGHT VIEW 20.000" [508] OUTDOOR AIR OPENING 20.000" [508] CONNECTION SIZES 14 gauge wire nut 3/4" mpt CONDENSATE DRAIN ACCESS DOOR 4.000" [102] 2.750" [70] 11.
24.500" [622] 3.530" [90] 8.000" [203] 4.000" [102] 8.000" [203] 1.750" [44] SUPPLY AIR OPENING EXHAUST AIR OPENING 20.000" [508] LEFT VIEW REVERSED DOOR OPTION 10.000" [254] 41.240" [1,047] CONTROL COVER LINE VOLTAGE IN 12.000" [305] CONTROL BOX DRY CONTACTS A 2.750" [70] 5.125" [130] Page 15 FRONT VIEW NOTE: A minimum of 12.000" [305] clearance from any obstruction is required for removal of the control box.
40.500" [1,029] 8.000" [203] 12.250" [311] 8.000" [203] 3.750" [95] Page 16 LEFT VIEW 15.250" [387] RETURN AIR OPENING OUTDOOR AIR OPENING 14.000" [356] 1.875" [48] 2.000" [51] RETURN AIR 2.000" [51] OUTDOOR AIR 3.625" [92] 8.000" [203] FRONT VIEW 51.000" [1,295] 24.736" [628] 31.080" [789] DEFROST AIR OPENING 47.000" [1,194] TOP VIEW 2.000" [51] 10.000" [254] ACCESS DOOR 10.605" [269] SUPPLY AIR OPENING B CONDENSATE DRAIN 7.500" [191] 8.000" [203] 10.750" [273] 8.
Page 17 10.000" [254] LINE POWER SUPPLY LEFT VIEW 10.000" [254] 5.250" [133] 7.625" [194] C 91.000" [2,311] 85.000" [2,159] 88.500" [2,248] 26.000" [660] FILTER ACCESS PANEL 48.500" [1,232] 50.500" [1,283] FRONT VIEW B D 30.000" [762] 4.000" [102] 12.000" [305] 48.500" [1,232] 46.000" [1,168] 44.375" [1,127] RETURN 23.250" [591] AIR OUTDOOR AIR FILTER ACCESS PANEL RIGHT VIEW 26.000" [660] 20.375" [518] OUTDOOR AIR OPENING 48.500" [1232] 26.000" [660] 26.
36.180" [919] Page 18 EXHAUST AIR OPENING 17.500" [444] 7.698" [196] LEFT VIEW OPTIONAL SUPPLY AIR OPENING HORIZONTAL 3.728" [95] 16.000" [406] 3.275" [83] 6.000" [152] 11.775" [299] 14.000" [356] 9.500" [241] OPTIONAL SUPPLY AIR 17.500" [444] 16.900" [429] 16.000" [406] LINE POWER SUPPLY 4.500" [114] EXHAUST AIR 4.520" [115] 6.500" [165] 8.325" [211] A 26.000" [660] 12.250" [311] 12.000" [305] VERTICAL OPENING SUPPLY AIR B CONDENSATE DRAIN 14.925" [379] 14.
Roofcurb Dimensions HRV2000e EXHAUST AIR TO OUTSIDE SEE DETAIL "B" RETURN AIR OUTDOOR AIR IN SUPPLY AIR SUPPLY AIR NOTE: Dimensions in [ ] are millimeters DETAIL "B" UNIT 3/8" [9.5] GASKET (Supplied With Curb) WOOD NAILER Overhang: 6.151" [156mm] RETURN AIR UNIT BASERAIL RETURN AIR OPENING 37.875" [962] COUNTER FLASHING (Field Supplied) 26.920" [684] 77.000" [1,956] 2.000" [51] ROOFING FELT (Field Supplied) 2.000" [51] CANT STRIP (Field Supplied) 13.
Electrical Data ODP MOTOR MEDIUM EFFICIENCY HRV600i, HRV700i, HRV1200i Blower Motor Specifications HRV600i HRV700i HRV1200i HP 1/4 1/6 1/3 Motor Voltage 120/1/60 120/1/60 120/1/60 Unit Specifications Motor FLA 3.8 2.5 5.9 Unit Voltage 120V 120V 120V MCA 9.5 6.6 14.3 MOP 12 9 20 Unit FLA 8.6 6.0 12.8 Blower Motor Full Load Amperage (FLA) HRV2000i/e HP 1/2 3/4 1.0 1.5 2.0 3.0 208/1/60 4.5 5.4 6.8 10.2 14.0 17.8 230/1/60 4.0 6.0 7.0 10.2 14.0 17.0 VOLTAGE 208/3/60 1.8 2.7 3.4 5.0 6.4 10.
Sequence Of Operation Before start-up, check the unit for obstructive packaging, objects near or in blowers, dampers, etc. Once installation is complete, close the doors and check for correct unit operation as described in the Ventilation Control section below. Ventilation Control Install the power to the unit as per local electrical codes and complete the following ventilation control modes to ensure proper unit operation.
Controls Data Wall Control Two types of remote wall controls are available: 1. Standard Wall Control: analog control with slide fan speed switch and dehumidistat adjustment. 2. Xtra Wall Control: digital control with push buttons for fan mode selection, dehumidistat control and maintenance indicator. The remote wall controls work with the integrated electronic controls within the unit to control ventilation sequences.
Options Frost Control The requirement for frost control is based upon the outdoor air temperature and humidity content of the return air. In areas where the winter outdoor air condition falls below 23°F [-5°C] or the return air relative humidity is above 20%, frost control is probably required. To verify the necessity of frost control, use the Venmar Select™ Software or contact a Representative. A large imbalance of airflows may alter these guidelines.
Options Dirty Filter Sensor The dirty filter sensor option will monitor the pressure across the filters and will close contacts when dirt restricts the airflow to the setpoint. The connections at the external terminal interface will close and can be used to control a remote light or alarm to signal dirty filters. The sensor has the following features: • Pressure setpoint is factory set. • Polyester film diaphragm responds to pressure changes as low as 2.5mm WC.
Door Fasteners HRV600i, HRV700i and HRV1200i Standard door access consists of quick release draw latches with compression pin hinges for full door removal. HRV2000i/e Standard filter door access consists of formed metal handles and screws that require a hex driver to remove them. Deluxe filter door access consists of molded plastic handles as well as quarter-turn door fastener upgrade.
Notes Page 26
Notes Page 27
Venmar CES Inc. Saskatoon, SK Canada www.venmarces.