Light Commercial Heat Recovery Ventilators Installation, Operation and Service Instructions VB0003 VB0002 600 cfm 700 cfm VB0001 1200 cfm 06/00 04597
Contents 1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Installation 2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2 Mounting Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.3 Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.4 Ductwork . . .
1 Safety Considerations 2.3 Mounting Options Hazards may exist within this equipment because it contains electrical and powerful moving components. Only qualified service personnel should install or service this equipment. Untrained personnel can perform basic maintenance such as maintaining filters. Observe precautions marked in literature and on labels attached to unit. Follow all safety codes. WARNING Disconnect main power switches to unit before performing service or maintenance.
The supply and exhaust ducts connected to outside, as well as any ducts passing through an unconditioned space, must have a minimum insulation value of R5. In addition, a continuous integral vapor barrier over the duct insulation must be used. Air balancing dampers are recommended for both supply and exhaust ducts to allow for adjustment of airflow.
2.8 Electrical Connections Power A terminal block and strain relief bushing or a junction box is provided for line voltage to make the necessary power connections. The electrical requirements are as follows: VOLTAGE MCA MOP 600 cfm 700 cfm 1200 cfm 115V 8.65 12.5 115V 6.63 9.13 115V 13.4 20 Control Box Access For Low Speed Setting (600 cfm/1200 cfm only) Disconnect power to the unit. Remove the four screws securing the cover plate as shown in Appendix F.
Recirculation Defrost Module (Optional - Factory Installed) The Recirculation Defrost Module is only available with the 600 cfm and 1200 cfm units. The defrost cycle is electronically controlled in response to the outside temperature 23°F to -22°F (-5°C to -30°C). On a call for defrost, the supply air damper in the recirculation module closes, exhaust fan is de-energized and the supply fan continues to recirculate warm air through the heat recovery core.
4.2 Balancing Procedure 1 Before proceeding with balancing, all windows, overhead doors and walk-in doors should be closed and exhaust systems should be turned off. 1 The connections between the flow stations and the ducts must be sealed with tape. Mount the magnehelic gauge in a convenient location where it is level and will not vibrate or be bumped. Zero the gauge. Measure the exhaust air first as it is often the lowest due to a longer duct system. VL0001 600 cfm and 1200 cfm 1.
Allow the heat recovery core to soak for three hours in warm water and mild soap. Rinse under a heavy stream of water. WARNING Hot water and a strong cleaning agent could damage the polypropylene core. Ensure the core is returned to the unit in the correct orientation. Use the sticker as a guide. Fans Blower wheels and fan housing should be checked for dirt build-up. If they appear dirty, it may be necessary to remove the blower assembly and then vacuum the dust out through the fan mouth.
Appendix A Mounting Diagrams 600 cfm and 1200 cfm NOTE: Diagrams show standard unit configuration. For units with the reversed door option, the door will be located here.
Page 10 4.000" [102] LEFT SIDE B SUPPLY AIR OPENING EXHAUST AIR OPENING 14.000" [356] 28.005" [711] 10.005" [254] A CONTROL BOX ACCESS LOW VOLTAGE TERMINAL STRIPS LINE POWER 4.028" [102] 5.859" [149] SUPPLY AIR EXHAUST AIR C 5.125" [130] RETURN AIR OUTDOOR AIR FRONT NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION, INTERIOR COMPONENTS WILL APPEAR AS A MIRROR IMAGE OF THE ABOVE DIAGRAM. 34.000" [864] TOP 19.207" [488] 13.375" [340] D B A B HRV600i ALUMINUM CORE PTS Kg LBS A 44.
Page 11 VK0004A Control Plate 3.53" [90] 8.00" [203] 4.00" 24.50" [102] [622] 8.00" [203] 4.00" [102] 1.75" [44] Control Box Dry Contacts Line Power 2.75" [70] 12.00" [305] 19.207" [488] 5.125" [130] 49.550" [1259] Heat Recovery Core Access Door Drain Fitting Access Door Strap Mounting Location 15.00" [381] Reversed Door Option 14.00" [356] 7.10" [180] 14.10" [358] Exhaust Air From Building Fresh Air From Outside A minimum of 15.
Page 12 LEFT SIDE B FRESH AIR TO BUILDING EXHAUST AIR TO OUTSIDE 20.000" [508] 11.325" [288] 4.028" [102] LINE POWER CONTROL BOX ACCESS LOW VOLTAGE TERMINAL STRIPS A 5.715" [145] SUPPLY AIR EXHAUST AIR C 5.125" [130] D RETURN AIR OUTDOOR AIR FRONT VIEW NOTE: FOR UNITS WITH THE REVERSED DOOR OPTION, INTERIOR COMPONENTS WILL APPEAR AS A MIRROR IMAGE OF THE ABOVE DIAGRAM. 34.000" [864] TOP 19.207" [488] 14.250" [362] B ACCESS DOOR 4.000" [102] 2.
3.53" [90] 8.00" [203] 24.50" 4.00" [102] [622] 8.00" [203] 1.75" [44] Entrée d’air frais Sortie d’air vicié 20.00" [508] 41.24" [1047] Page 13 VK0003F Couvercle du boîtier Boîtier électronique Borniers Alimentation électrique 2.75" [70] 12.00" [305] Un dégagement minimum de 12.00" [305] est requis pour retirer le boîtier électronique. Option de porte inversée 10.00" [254] 5.
Page 14 VK0002A 40.500" [1029] 8.000" [203] 12.250" [311] 8.000" [203] 3.750" [95] LEFT SIDE 15.250" [387] RETURN AIR OPENING OUTDOOR AIR OPENING 14.000" [356] 1.875" [48] 3.625" [92] RETURN AIR 2.000" [51] OUTDOOR AIR CONDENSATE DRAIN B 2.000" [51] 8.000" [203] 2.000" [51] 10.000" [254] SUPPLY AIR OPENING EXHAUST AIR OPENING 7.500" [191] 8.000" [203] 10.750" [273] 8.000" [203] 1.875" [48] RIGHT SIDE 10.605" Low Voltage [269] Terminal Strips A minimum of 12.
Appendix C Flow Station Positions 600 cfm and 1200 cfm Reverse Door Option Balancing Damper Flow Measuring Station (FMS) Min. 8" (203mm) (Optional) Canvas Vibration Isolator Fresh Air From Outside Min. 12" (305mm) Min. 30" (762mm) VP0001A Exhaust Air From Building Canvas Vibration Isolator Min. 12" (305mm) 700 cfm Flow Measuring Station (FMS) Balancing Damper (not supplied) Min.12" (304mm) VP0002A Canvas Vibration Isolator Dry Contacts Min. 30" (762mm) Page 15 Min.
Appendix D Drain Connections 600 cfm and 1200 cfm Note: All hose, pipe & couplers to be supplied by others Plastic Drain Fittings 3/4"NPT Coupler To Drain Plastic Hose Copper or Plastic Pipe Water Trap T D i 700 cfm Plastic Drain Fitting Note: All hose, pipe, and couplers to be supplied by others.
Appendix E Terminal Control Diagrams E-2: Wall Control Connection E-1: Terminal Label A low voltage remote control wiring interface is provided on the unit. The connections for the low voltage remote wiring are located on two terminals adjacent to the exhaust fan outlet (or adjacent to the supply fan outlet on the 700 cfm unit). All field installed wiring must be low voltage class II. Four types of remote wall controls are available: 1. Slide Switch Wall Control with fan switch and dehumidistat control 2.
Appendix E Continued Terminal Control Diagrams E-3: Occupied Timer/Sensor Connection E-4: Remote Fan Control Occupancy control is achieved by connection to the terminal interface shown below. These terminals require a dry contact which could be provided by a number of types of controls such as a timer, light sensor, occupancy sensor, building management system, or other.
Appendix F Electrical Connection Diagrams Control Box Assembly 600 cfm and 1200 cfm Remote control access plate Remote wiring terminal block Control box HRV Cabinet Control cover plate VE0001A Low Speed Setting Wire Connections 600 cfm and 1200 cfm 12 pin 2 pin LOW SPEED SETTING To change the minimum speed setting from Low To Medium, move the fork connector: from here to here d Re ABCDEFG J4 J2 6 9 321 4 7 1 J3 JU1 Remove power before installing or removing JU1-F Extended Defrost Jumper FF1 O
283 259 236 212 600 550 500 450 Page 20 11.5 3.2 4.0 5.1 6.3 7.0 7.8 8.6 3.9 4.8 5.9 7.2 8.0 8.9 9.7 kW 73°F(23°C) 11.2 519 495 472 425 377 330 1150 1100 1050 1000 900 800 700 5.1 7.0 8.5 9.9 10.7 8.1 10.4 12.4 14.1 15.2 15.9 17.4 18.6 19.9 9.3 11.7 13.8 15.7 16.9 17.7 19.3 20.6 21.9 kW 73°F(23°C) 3.7 5.2 6.4 7.4 8.1 8.5 9.6 10.4 11.2 kW 55°F(13°C) 6.7 8.6 10.2 11.7 12.6 13.2 14.5 15.5 16.5 kW 68°F(20°C) 7.9 9.9 11.
COMM. N/C N/O -t DEFROST TEMP. SENSOR JU1 VE0023A 48445 POWER CONTROL BOARD J1 3 2 1 .. .. .. 2 1 J4 2 3 J2 1 W BL BL G J3 1 J3 2 J3 8 O J1 6 W W J1 2 J1 1 BK/R J1 9 J1 8 BK R J1 3 J1 5 J1 4 R J3 7 AUTOTRANSFORMER CONTROL BOX WALL CONTROL GREEN WALL CONTROL YELLOW LOW SPEED (3.
VE0024A CONTROL BOX COMM. N/C N/O JU1G - INTERMITTENT STANDBY (SI) JU1 - F EXTENDED DEFROST 48444 POWER CONTROL BOARD -t JU1 J2 1 2 1 .. .. ..
COMM. N/C N/O -t .. .. .. VE0022A 48445 POWER CONTROL BOARD J1 2 J1 9 W NO NC R3-1 NO COM COM NO COM NO NO COM R3-4 COM NO W R4-2 BK W W/BL BK/Y MEDIUM SPEED CONNECTIONS 10 A NOTE 1 R4-1 OUTPUT NC Y COM BK W INPUT COMMON O BK/R BK J1 3 J1 6 W J1 1 BL J1 7 CONTROL BOX WALL CONTROL GREEN WALL CONTROL YELLOW LOW SPEED (3.
Appendix I Trouble Shooting SYMPTOMS POSSIBLE CAUSES SOLUTIONS Inside air is too dry Over ventilation - speed setting too high Dehumidistat setting is too low Adjust speed setting Set dehumidistat control in a higher position (if applicable) Persistent condensation on windows, walls, ceilings, etc.