Technical data

4
1. TECHNICAL DATA
1.1 AIR DISTRIBUTION (NORMAL OPERATION)
1.3 D
EFROST CYCLES TABLES
HRV CONSTRUCTO 1.5ES AND SOLO 1.5ES UNITS
OUTSIDE TEMPERATURE DEFROST CYCLES (MINUTES)EXTENDED DEFROST CYCLES
CELCIUS (°C) FAHRENHEIT (°F) DEFROSTING
OPERATION TIME BETWEEN EACH
DEFROST CYCLES
DEFROSTING
OPERATION TIME BETWEEN EACH
DEFROST CYCLES
-5 23 7 50 10 30
-15 5 7 25 10 20
-27 -17 10 20 10 15
1.2 AIR DISTRIBUTION (DEFROST MODE)
VF0052
VF0053
ERV CONSTRUCTO 2.0 ES UNIT
OUTSIDE TEMPERATURE DEFROST CYCLES (MINUTES)EXTENDED DEFROST CYCLES
CELCIUS (°C) FAHRENHEIT (°F) DEFROSTING
OPERATION TIME BETWEEN EACH
DEFROST CYCLES
DEFROSTING
OPERATION TIME BETWEEN EACH
DEFROST CYCLES
-5 23 10 60 10 30
-15 5 10 30 10 20
-27 -17 10 20 10 15
HRV CONSTRUCTO 2.0ES AND SOLO 2.0ES UNITS
OUTSIDE TEMPERATURE DEFROST CYCLES (MINUTES)EXTENDED DEFROST CYCLES
CELCIUS (°C) FAHRENHEIT (°F) DEFROSTING
OPERATION TIME BETWEEN EACH
DEFROST CYCLES
DEFROSTING
OPERATION TIME BETWEEN EACH
DEFROST CYCLES
-5 23 6 50 10 30
-15 5 6 25 10 20
-27 -17 10 20 10 15
NOTE: The Constructo and Solo Performance Charts are listed on the specification sheets of these units.
Visit our website at www.venmar.ca to access those documents.