User's Manual

37
Main Menu Buttons - Settings
Installation Settings
Heat & Cool Stages
(1h1c)
Heat & Cool Stages
(1h1c)
Up to 2 Stages Cooling and 4 stages Heating.
Compressor Stages
(1h1c)
Up to 2 compressors.
Aux Heat Stages
(1h1c)
0 to 2 stages of Aux Heating.
Compressor Min OFF Time
(5m)
None, 1 minute, or 5 minutes.
At 6 cycles per hour, the HVAC unit will only be allowed to
energize once every 10 minutes. The Cycles Per Hour limit
may be overridden and reset by pressing the WARMER or
COOLER buttons. (2, 3, 4, 5, 6, No Limit)
Cycles Per Hour
(6)
Min Heat/Cool Difference
(2˚)
The minimum gap between Heat and Cool setpoints. (0 - 6 deg. F)
Timers & Deadbands
}
Only available when
dip switch is set for
Heat Pump operation.