User's Manual

8
Step 4 - Label&DisconnectWires
1) Onebyone,applyalabel
designated to each wire
you disconnect from
your current thermostat.
TIP:Beforedisconnectinganywires,
take a photo of your current wire
configurationwithyourmobiledevice.
Wirefromthe Installonthe
oldthermostat Function newthermostat Wire
terminal marked connector marked Color
G or F Fan G
Y1,Y Cooling Y1
W1,W Heating W1/0/B
Rh,R,M,Vr,A Power R
C Common C
O/B Rev.Valve W1/O/B*
W2 2ndStageHeat W2
Y2 2ndStageCooling Y2
W3 3rdStageHeat W3
H,Hum Humidity HUM
D,Dehum Dehumidity DEHUM
Ck1 DryContactSwitch DRYCONTACT
CKGND DryContactSwitch DRYCONTACT
*O/BisusedifyoursystemisaHeatPump.